tekmar 363 Universal Reset Control Installation User Manual

Page 25

Advertising
background image

25 of 40

Copyright © D 363 -

12/08

363 Adjust Menu (2 of 5)

D1

The starting water temperature used in the reset
ratio calculation for the mixed supply.

DIP switch =

Reset Ratio

35 to 150˚F
(2 to 66˚C)

Default = 70

°F (21°C)

D1

The design supply temperature used in the heat
loss calculation for the mixing system.

70 to 220˚F
(21 to 104˚C)

Default = 120

°F (49°C)

D1

The outdoor starting temperature used in the
reset ratio calculation for the heating system.

DIP switch =

Reset Ratio

35 to 85˚F
(2 to 29˚C)

Default =70

°F (21°C)

B1

D1

The design outdoor air temperature used in the
heat loss calculation for the heating system.

-60 to 32˚F
(-51 to 0˚C)

Default = 10

°F (-12°C)

D1

The maximum supply

target temperature for the

mixing system.

80 to 210˚F, OFF
(27 to 99˚C, OFF)

Default = 140

°F (60°C)

D2

The type of mixing device that is to be used in
the heating system.

FLOT (Floating),
VAR (Variable speed),
STOR (Storage)

Default = VAR

D2

The time that the actuating motor requires to
operate from fully closed to fully open.

MIXING = FLOT

30 to 230 sec

Default = 160 sec

C1

The device that is to be connected to the 10K 2
input terminal.

NONE, DHW, STOR
(Storage tank)

Default =

NONE

E3

The polling time that is to be used for a storage
tank.

MIXING = STOR
10K 2

≠ STOR

0:20 to 12:00 hr

Default = 1:00 hr

D1

The design indoor air temperature used in the
heat loss calculation for the mixing system.

DIP switch =

Characterized Heating Curve

35 to 100˚F
(2 to 38˚C)

Default =70

°F (21°C)

Actual

Setting

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER