Adjust menus – tekmar 363 Universal Reset Control Installation User Manual

Page 24

Advertising
background image

24 of 40

Copyright © D 363 -

12/08

D1

D1

D3

B2

B2

D3

D3

A

D1

A

363 Adjust Menu (1 of 5)

Occ

D1

The desired room air temperature during an
Occupied period for mixing zone(s).

Note: There

is only a

±3°F adjustment in the LTD access level.

DIP switch =

Characterized Heating Curve

No RTU connected

35 to 100˚F
(2 to 38˚C)

Default = 70

°F (21°C)

35 to 100˚F
(2 to 38˚C)

Default = 65

°F (18°C)

UnOcc

The desired room air temperature during an
UnOccupied period for mixing zone(s).
DIP switch =

Characterized Heating Curve

DIP switch =

Setback

No RTU connected

NONE, INDR (Indoor),
MIX (Mixing zone
control), Boil

(Boiler

zone control), SLAB

Default = NONE

NONE, Boil (Boiler
zone control)

Default = NONE

The device that is to be connected to the 10K 1
input when an RTU is not connected.

DIP switch =

Characterized Heating Curve

No RTU connected

The device that is to be connected to the 10K 1
input when an RTU is connected.

DIP switch =

Characterized Heating Curve

RTU is connected

OFF, 35 to 120˚F
(OFF, 2 to 49˚C)

Default = 70

°F (21°C)

40 to 150˚F
(4 to 66˚C)

Default = 90

°F (32°C)

The minimum temperature at the slab sensor

DIP switch =

Characterized Heating Curve

No RTU connected
10K 1 = SLAB

OFF, 0:20 to 8:00 Hr.

Default = OFF

The maximum temperature at the slab sensor.

DIP switch =

Characterized Heating Curve

No RTU connected
10K 1 = SLAB

The

maximum length of morning boost.

DIP switch =

Characterized Heating Curve

DIP switch =

Setback

No RTU connected
10K 1

≠ MIX

The amount the mixing supply water temperature
will be reduced when the control is in the
UnOccupied mode.

DIP switch =

Reset Ratio

DIP switch =

Setback

0 to 50˚F
(0 to 28˚C)

Default = 9

°F (5°C)

The type of terminal units that are being used for
the mixing side of the system.

DIP switch =

Characterized Heating Curve

HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)

Default = HRF1

The minimum supply water temperature for the
mixing system.

DIP switch =

Characterized Heating Curve

OFF, 35 to 150˚F
(OFF, 2 to 66˚C)

Default = OFF

Actual

Setting

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER