tekmar 363 Universal Reset Control Installation User Manual

Page 11

Advertising
background image

11 of 40

Copyright © D 363 -

12/08

Section C3 —DHW with Low Temperature Boilers (without Mixing)

If DHW is to be incorporated into a low temperature system such as a radiant heating system, a mixing device is often installed to isolate
the high DHW supply temperature from the lower system supply temperature. If a mixing device is not installed, high temperature water
could be supplied to the low temperature system while trying to satisfy the DHW demand. This may result in damage to the low
temperature heating system. The 363 is capable of providing DHW in such a system while ensuring that the low temperature in the
heating system does not exceed its allowed maximum setting.

To prevent high temperature water from being introduced into the heating system, the Boiler Pump (P1) must be turned off during a
call for DHW. To do this, DHW THRU must be set to PUMP, DHW PRI must be set to B + M, and Boil MIN must be set to OFF.

On a call for DHW, the 363 provides DHW priority by shutting off the Boiler
Pump (P1) for a period of time. This time is based on the outdoor air
temperature as described in the DHW Priority Override section. If the

DHW

Demand is not satisfied within the allotted time, the boiler shuts off and the
boiler’s heat is purged into the DHW tank.

Once the boiler supply temperature is sufficiently reduced, the DHW pump
shuts off. Then the heating system is turned on for a period of time to
prevent the building from cooling off. After a period of heating, if the DHW
demand is still present, the 363 shuts off the heating system and provides
heat to the DHW tank once again.

For correct operation, close attention must be paid to the mechanical layout of the system. When the 363 turns off the Boiler Pump (P1),
flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the maximum desired
temperature and can result in damage to the heating system.

Section C4 —Setpoint

The 363 can handle setpoint loads which are high temperature loads connected to the boiler loop that are not heating loads or DHW.
For this feature to be available, either a DHW sensor must be used or the DHW THRU item is set to NONE. If an external DHW demand
is used as described in Section C1, you cannot use the setpoint feature.

SETPOINT DEMAND

The 363 registers a

Setpoint Demand when a voltage between 24 and 240 V (ac) is applied

across the

Setp / DHW and the Com Dem terminals (5 and 3). Once voltage is applied, the

setpoint demand pointer turns on in the LCD. The control operates the boiler to maintain at
least the boiler supply temperature as set by the SETPOINT

Occ setting. The Setpoint Demand

does not turn on the Boiler Pump (P1). If a setpoint load is used, the installer must make sure
that the setpoint device provides its own flow through the boiler.

BOILER TARGET DURING SETPOINT (Boil TRG)

The Boil TRG temperature during a

Setpoint Demand is increased to at least the SETPOINT

setting. This temperature is maintained as long as the 363 has a

Setpoint Demand.

SETPOINT SETBACK (SETPOINT UnOcc)

If the 363 is placed into setback, the

Setpoint Dem is ignored if the SETPOINT UnOcc setting is set to OFF. Otherwise, the setpoint

operates normally. If a system override of AWAY is selected, the 363 operates the SETPOINT load at the

Occupied setting.

SETPOINT PRIORITY (SETP PRI = B+M)

For setpoint loads to have priority over the Boiler and Mixing zones, set SETP PRI to B + M. If this option is chosen, the output from
the mixing device is suspended and the Boiler Pump (P1) turns off during a

Setpoint Demand.

Priority Override



In order to prevent the building from cooling off too much or the possibility of a potential freeze up during setpoint priority, the 363 limits
the amount of time for setpoint priority. As the outdoor air temperature becomes colder, the length of time the 363 provides setpoint
priority is reduced. Once the allowed time for priority has elapsed, the 363 overrides the setpoint priority and operates setpoint and
heating simultaneously.

Conditional Setpoint Priority



If the Boil SUP temperature is maintained at or above the required temperature during setpoint generation, this indicates that the boiler
has enough capacity for setpoint and possibly heating as well. As long as the Boil TRG temperature is maintained, setpoint and heating
occur at the same time.

Sequence, Section C3

3

4

Com

Dem

Boil

Dem

Setp/

DHW

5

24 to 240 V (ac)

P

P1

DHW

Advertising