Table A-2

AC Electrical Specifications

Description

Value

Total AC Input Power

3000 VA (volt-amps) per AC power supply

(2 AC power supplies per system)

Rated input voltage

1

1.

For each AC power supply module.

200–240 VAC nominal (range: 180 to 264 VAC)

220–240 VAC (UK)

Rated input line frequency

1

50/60 Hz nominal (range: 47 to 63 Hz)

50/60 Hz UK

Input current rating

1

15 A maximum @ 200 VAC

13 A maximum @220 to 240 VRMS (UK)

Source AC service
requirement

1

20 A North America; 16 A international;
13 A UK

Heat dissipation

(total maximum)

2800 W@9,544 BTU/hour

Redundancy

2 AC power supply modules required for 2N
redundancy

Table A-3

DC Electrical Specifications

Description

Value

Total DC Input Power

2800 W per DC power entry module

Rated input voltage

1

–48 VDC nominal in North America

–60 VDC nominal in the European Community

(range: –40.5 to –72 VDC (–75 VDC FOR 5mS))

Input current rating

1

40 A maximum (2x)