3. SYSTEM DESCRIPTION

1. Input Type (Operating Mode) LED:

2. Voltage Range (Output Voltage Mode) LED:

l

l

l

Normal mode: The Yellow LED indicator will illuminate during normal

mode, the UPS accepts AC input voltage range from +/-20%.

Generator: No change to voltage window. However, the low frequency

transfer point is changed to 40Hz and there is no limitation for high frequency
transfer point.

Wide range: The LED indicator will illuminate, the UPS accepts AC input

voltage range from -30% ~ +20%.

UPS Output voltages selection: 110VAC/120VAC/127VAC or
220VAC/230VAC/240VAC.

7. Bad Battery LED:

8. Overload LED:

9. Fault LED:

The LED indicator will flash every two seconds when the battery has failed, or
if the battery is disconnected. Please check your battery connection; replace
the battery or contact your local dealer for a battery replacement kit.

The LED indicator will light when the UPS is overloaded.

The LED indicator will light when the UPS fails/overload or battery
timeout/no output.

INPUT TYPE

NORMAL

GENERATOR

WIDE RANGE

VOLTAGE RANGE:

VOLTAGE RANGE:

110VAC

220VAC

120VAC

230VAC

127VAC

240VAC