Smart Power Systems SSP UPS User Manual

Page 38

Advertising
background image

35

6. BATTERY REPLACEMENT

7. Slide the new batteries into EBM.
8. Reconnect the battery cable and screw the battery bracket.
9. Close and reinstall the front panel back to EBM.

7. COMMUNICATION PORT

7.1 RS232 + Dry contact (750/1000/1500/2000/3000VA):

DB9 Female (RS232 +dry contact)

7.2 USB port: HID protocol

The USB and RS232 are unable to operate at the same time. Either the USB

or DB9 can connect with RS-232 at one time, usually connecting with USB

function is priority.

PIN #

Description

I/O

Function Explanation

1

DCD

Output

Low Battery Output
(*normally open, pull to
Pin# 5 when battery low
alarm in battery mode)

2

RxD

Output

RxD

3

TxD

Input

TxD

4

5

Common

--

6

DSR

Output

7

RTS

Input

No connection

8

(tied to pin 6)

Input

DTR

Common (tied to chassis)

(tied to pin 4)

AC Fail Output
(*normally open, pull to
Pin#5 when UPS is in
battery mode).

Output

CTS

Advertising