Specifications – Smart Power Systems SSP UPS User Manual

Page 41

Advertising
background image

38

MODEL

CAPACITY

INPUT

OUTPUT

OVERLOAD

RATING

TRANSFER

TIME

BATTERY

750 / 500

SSP750

1500 / 1050

SSP1500

2000 / 1340

SSP2000

3000 / 2100

SSP3000

VA / Watt

Voltage

Voltage
Range

Acceptable
Voltage Range

Line Low
Transfer (Wide
mode)

Line High
Transfer

Frequency Range

Surge Rating ( LV/HV )

Voltage

Voltage Regulation (Batt.
Mode)

Frequency

Frequency Regulation
(Batt. Mode)

Waveform

Line Mode

Battery Mode

Typical

Backup Time (at full load)

Recharge Time

110/120/127VAC or 220/230/240VAC

0-160VAC / 0-300VAC

77/84/89VAC ± 4% or 154/161/168VAC ± 4%

132/144/152VAC ± 2% or 264/276/288VAC ± 4%

50/60Hz ±5Hz for Normal Mode; >40Hz for Generator Mode

320 / 230 Joules

110/120/127VAC or 220/230/240VAC

±5% RMS for entire battery voltage range

50Hz or 60Hz

±0.1Hz

Pure Sinewave

110% -0%, +8%; shutdown after 3 minutes. 150% -0%, +10%;

Shutdown after 10 cycles

110% ± 6%; shutdown after 30 seconds. 120 % ± 6 %;

Shutdown after 5 cycles

2-4ms Typical, 6 ms max ; 13ms max. for generator mode

500 / 640

Joules

430 / 250 Joules

5 minutes min.

3 hours to 90% after discharged

9. SPECIFICATIONS

1000 / 700

SSP1000

Advertising