9. If proper pilot flame profile is present and flame sense current is in range, the pilot gas valve

will stay open.

10. After the main burner delay time (30 sec) is complete the main burner will light.

11. The pilot will stay lit and the combustion blower will stay on as long as the call for heat

switch is on.

12. Hereafter, because the pilot stays on, the main burner will turn on and off immediately when

the heat relay in the temperature control closes.