1 general information – Bradford White BNTV-600 User Manual

Page 12

Advertising
background image

Page 8

B

RADFORD

W

HITE

C

ORP.

Section 2 -

LOCATING THE APPLIANCE

2.1 General Information

The Brute Elite unit is designed for indoor installations
only.

The appliance should be located to provide clearances on all
sides for maintenance and inspection. It should not be located
in an area where leakage of any connections will result in

damage to the area adjacent to the appliance or to lower floors
of the structure.

When such a location is not available, it is recommended that
a suitable drain pan, adequately drained, be installed under the
appliance.
The appliance is design certified by CSA-International for

installation on combustible flooring; in basements; in closets,
utility rooms or alcoves. Brute Elite Boilers must never be
installed on carpeting.
The location for the appliance should
be chosen with regard to the vent pipe lengths and external
plumbing and on a level surface. The unit shall be installed
such that the gas ignition system components are protected

from water (dripping, spraying, rain, etc.) during operation

and service (circulator replacement, control replacement, etc.).
When vented vertically, the Brute Elite must be located as
close as practical to the vertical section of the vent. If the vent

terminal and/or combustion air terminal terminate through a
wall, and there is potential for snow accumulation in the local
area, both terminals should be installed at an appropriate level
above grade or the maximum expected snow line.
The dimensions and requirements that are shown in Table 1
should be met when choosing the locations for the appliance.

2.2 Locating Appliance for Correct Vent

Distance from Outside Wall or

Roof Termination

The forced draft combustion air blower in the appliance has

sufficient power to vent properly when the guidelines in Table
2

are followed.

NOTE: When located on the same wall, the Brute Elite

combustion air intake terminal must be installed a

minimum of 12” below the exhaust terminal.Models 399-

850 also require a minimum horizontal distance from

intake to exhaust terminal of 36”.
For concentric vent terminal kit (optional), follow installation
instructions included with the kit.

APPLIANCE

SUGGESTED SERVICE ACCESS CLEARANCE

SURFACE

INCHES

CM

Left Side

1

2.5

Right Side

12

31

Top

24

61

Back

6

15

Closet, Front

(285-500)

6

15

Alcove, Front

(285-500)

24

61

Front

(600-850)

24

61

Vent

Certified by CSA for zero clearance to

combustible materials on all sides.

Table 1 - Clearances

INTAKE / EXHAUST

STANDARD MAX EQUIV.

OPTIONAL

MAX EQUIV.

SIZE VENT

FT.

M VENT

FT.

M

80 2”

40

6.1 3”

100

30.5

105 2”

40

6.1 3”

100

30.5

150 3”

100 30.5

n/a — —

199/210 3”

100 30.5

n/a — —

285 4”

100

30

n/a — —

399 4”

100

30

n/a — —

500 4”

100

30

n/a — —

600* 4”

40

6.1 6”

100

30

750 4”

40

6.1 6”

100

30

850 4”

40

6.1 6”

100

30

Installations in the U.S. require exhaust vent pipe that is a combination
of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless
steel complying with UL1738. Installations in Canada require exhaust
vent pipe that is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM
D1785 F441, ABS that complies with ANSI/ASTM D1527 or galvanized
material.
The installer must comply fully with the manufacturer’s installation
instructions, including use of minimum exhaust length CPVC, to main-
tain ANSI Z21.13 safety certification.
Closet and alcove installations do not allow the use of PVC under any
circumstances
To calculate max equivalent length, measure the linear feet of the pipe,
and add 5 feet (1.5m) for each 90°

*

elbow used.

* For any combination of vent and intake lengths up to 40 equivalent
feet, any even or uneven combination of length is allowed. For overall
lengths greater than 40 equivalent feet, the exhaust may be up to 20
feet greater than the intake length.

Table 2 - Vent / Air Pipe Sizes

*

Add 2

1/2

feet (.76 meters) for each 45 elbow used.