1 brute elite boiler flow and head requirements – Bradford White BNTV-600 User Manual

Page 20

Advertising
background image

Page 16

B

RADFORD

W

HITE

C

ORP.

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY

UNDILUTED PROPANE

NOMINAL PIPE SIZE

@

11” W.C. INLET AND 0.5” W.C. PRESSURE DROP

SIZE

1/2” 3/4” 1” 1-1/4”

1-1/2” 2”

LENGTH

MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR

20 200 418 787 1616 2422 4664
40 137 287 541 1111 1664 3205
60 110 231 434 892 1337 2574
80 94 197 372 763 1144 2203

100 84 175 330 677 1014 1952

NOTES:
1. Follow all local and national LP gas codes for line sizing and equipment

requirements.
2. Verify that inlet gas pressure remains between 4 and 13 inches of water

column before and during operation.

Source: ANSI Z223.1-80 National Fuel Gas Code.

Table 6d

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING

1/2” 3/4” 1” 1-1/4”

1-1/2” 2”

LINEAR FEET

90° ELBOW

3.6 4.4 5.2 6.6 7.4 8.5

TEE

4.2 5.3 6.6 8.7 9.9 12

Table 6b

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS

NOMINAL PIPE SIZE

@

0.30” W.C. PRESSURE DROP

LENGTH

1/2” 3/4” 1” 1-1/4”

1-1/2” 2”

FT

CUBIC FEET OF GAS PER HOUR

20 92 190 350 730 1100 2100
40 130 245 500 760 1450
60 105 195 400 610 1150
80 90 170 350 530 990

100

150 305 460 870

Table 6c

Brute Elite

NATURAL GAS

REQUIRED

CU FT

SIZE

/ HR.

80

80

105 105
150 150

199/210 199/210

285 285
399 399
500 500
600 600
750 750
850 850

Table 6a

TO SIZE PIPING:

Measure linear distance from meter outlet to last

boiler. Add total input of all boilers and divide

by 1000 to obtain cu ft / hr required. Add total

equivalent length of fittings used according to

Table 6B. Align total length (pipe and fittings) on

left side column of Table 6C with highest cubic

feet of gas required.

Notes:

Consult and confirm with Applicable Fuel Gas

Code before beginning work. Verify gas inlet

pressure is between 4 and 13 in W.C. before

starting boiler.

Section 5 -

PUMP REQUIREMENTS

5.1 Brute Elite Boiler Flow and Head

Requirements

NORMAL WATER*

Flow H/L Temp

Flow H/L Temp

Size

gpm feet Rise °F

lpm

m

Rise °C

150

19 49 15

72 14.9 8

199

25 28 15

95 8.5 8

285

36 33 15

98 10.1 8

399

50 35 15 189 10.7 8

500

63 28 15 239 8.5 8

600

**

60 24 19 227 7.3 11

750

**

68 35 21 257 10.7 12

850

**

68 26 24 257 7.9 13

* Maximum water hardness of 10 grains per gallon allowed.

** See section 6B.7 on page 27 for pump information.

Table 8 - Water Heater Flow Data

5.2 Brute Elite Water Heater Flow and

Head Requirements

TEMPERATURE RISE IN °F

20°F

25°F

30°F

35°F

40°F

FLOW H/L FLOW H/L FLOW H/L FLOW H/L FLOW H/L

SIZE GPM FT GPM FT GPM FT GPM FT GPM FT

80 7.6 14.9 6.1 10.1 5.1 7.1 4.3 5.8 3.8 4.6
105 10 23.1 8 17 6.7 12.4 5.7 9.6 5 7.6
150 14.3 28.5 11.4 19 9.5 13.6 8.1 11.2 7.1 8.8
210 20 24.1 16 16.7 13.4 11.6 11.3 9 9.9 6.9
285 27 25.5 22 17.5 18 14 15 10.5 13 8
399 39 28 31 20 25 14.5 22 11 19 9
500 48 24 38 16 32 12 27 9 24 8
600 58 44 46 31 38 22 33 18 29 15
750 72 37 58 23 48 17 41 13 36 10
850 81 33 65 22 54 15 46 10 41 8

TEMPERATURE RISE IN °C

11°C 14°C 17°C 19°C 22°C

FLOW H/L FLOW H/L FLOW H/L FLOW H/L FLOW H/L

SIZE lpm m lpm m lpm m lpm m lpm m

80 29 4.5 23 3.1 19 2.2 16 1.8 14 1.4
105 38 7.0 30 5.2 25 3.8 22 2.9 19 2.3
150 54 8.7 43 5.8 36 4.1 31 3.4 27 2.7
210 76 7.3 61 5.1 51 3.5 43 2.7 37 2.1
285 102 7.8 83 5.3 68 4.3 57 3.2 49 2.4
399 148 8.5 117 6.1 95 4.4 83 3.4 72 2.7
500 182 7.3 144 4.9 121 3.7 102 2.7 91 2.4
600 220 13.4 174 9.4 144 6.7 125 5.5 110 4.6
750 273 11.3 220 7.0 182 5.2 155 4.0 136 3.0
850 307 10.1 246 6.7 204 4.6 174 3.0 155 2.4

Table 7 - Water Flow Requirements