Page 11

BRUTE ELITE

All installations should be done following the vent supplier’s
recommended installation techniques. If manufacturer’s
instructions are not available for the material used, follow the
Bradford White recommendations.

The vent pipe must pitch upward, toward the vent terminal,

not less than 1/4” per foot, so that condensate will run back
to the Brute Elite to drain. Route vent pipe to the heater as
directly as possible. Seal all joints and provide adequate
hangers as required in the venting system manufacturer’s
Installation Instructions. Horizontal portions of the venting
system must be supported to prevent sagging and may not
have any low sections that could trap condensate. The unit
must not support the weight of the vent pipe. Please see Table
2 for proper diameter vs. length allowed.

IMPORTANT NOTE ABOUT COMMON VENTING: A

single vent that is shared by multiple Brute Elite units

MUST be engineered by a competent venting specialist,

and involves the selection of draft inducing equipment,

hardware and controls to properly balance flue gas

pressures.

Do not common vent Brute Elite units

unless the vent system meets this requirement.

Brute Elite units are never permitted to share a vent

with Category I appliances.

Venting Requirements Unique to Canada
Brute Elite boilers and water heaters are Vent Category IV

appliances. Per the requirements of CAN/CSA-B149.1,
only BH vent systems can be connected to these units and

such vent systems, either ULC S636 certified stainless steel

or other ULC S636 certified BH vent (eg. plastics) must be

installed per the vent manufacturer’s certified installation
instructions.
As a result, two items listed in the Unpacking section (Figure

8) are not included with Brute Elite units for Canada

(underlined):

A

exhaust vent terminal (not included)

B.

air intake terminal

C.

temperature/pressure gauge kit

D.

circulator pump/wire harness (units with pump)

E.

CPVC exhaust pipe section (80-500) (not incl.)

F.

outdoor/system sensor kit

G.

flow switch kit (399-850)

H.

alternate size vent/terminal screens

J.

exhaust vent adapter CPVC/ST ST (750-850)

It is the responsibility of the appropriately licensed technician

installing this Brute Elite unit to use ULC S636 certified vent
material consistent with the requirements as described in the
Venting and Combustion Air section.

Class I venting systems are suitable for gas-fired appliances

producing flue gas temperature of more than 135°C, but not

more than 245°C.

Class II venting systems are suitable for gas-fired appliances

producing flue gas temperatures of 135°C or less.
Class II venting systems are further classified into four
temperature ratings as follows:

A

Up to and including 65°C

B

Up to and including 90°C

C

Up to and including 110°C, and

D

Up to and including 135°C

IMPORTANT! It is also the responsibility of the installer

to ensure that a flue gas sampling port is installed in the vent

system. This flue gas sampling port must be installed near the

flue connection of the Brute Elite unit: within 2 feet of the

flue connection. There is no flue gas sampling port internal
to the Brute Elite, so one must be installed in the vent system

external to the Brute Elite unit. A flue gas sampling port

available as a component of the ULC S636 certified vent
system is preferred. However, if one is not available with

the certified vent system, Bradford White suggests using a
tee with the branch connection sized to allow for insertion

of a flue gas analyzer probe. The branch connection must be
resealable with a cap or other by other means to ensure the

vent system remains sealed. (See Figure 11.)
Consideration must be given to the placement and orientation

of the flue gas sampling port to ensure that condensate is free

to flow back into the Brute Elite unit and not collect anywhere

in the vent system - including in the flue gas sampling port.
An exhaust vent terminal must be installed. If an exhaust

vent terminal is not available with the certified vent system,

Bradford White suggests the use of a coupler fitting from the

certified vent system into which the vent terminal screen,

Figure 11 - Test Port - ULC-S636 system