132

Fan speed failed during run

H

1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change

speeds.
3. Change the VFD
4. If the fault persists, replace the module.

137

ILK (Interlock) failed to close

H

1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper function.
3. Verify voltage through the interlock string to the interlock input with

a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.

149

Flame detected

H or L Create a Hold if a flame is detected during Safe Start check up to

Flame Establishing period.

150

Flame not detected

H

Sequence returns to standby and restarts sequence at the beginning

of Purge after the HF switch opens if flame detected during Safe Start

check up to Flame Establishing period.

154

Purge Fan switch On

H or L 1. Purge fan switch is on when it should be off.

2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and its connections.

Make sure the switch is working correctly and is not jumpered or

welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

155

Purge fan switch Off

H or L 1. Purge fan switch is off when it should be on.

2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and its connections.

Make sure the switch is working correctly and is not jumpered or

welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

156

Combustion pressure and flame

On

H or L 1. Check that flame is not present in the combustion chamber. Correct

any errors.
2. Make sure that the flame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the

flame detector.
5. Reset and sequence the module, if code reappears, replace the

module.

157

Combustion pressure and flame

Off

L

1. Check that flame is not present in the combustion chamber. Correct

any errors.
2. Make sure that the flame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the

flame detector.
5. Reset and sequence the module, if code reappears, replace the

module.

158

Main valve On

L

1. Check the main valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the

module.

Code Description

L or H Procedure