1 combustion air, Page 9, Table 4 - required combustion air pipe material – Bradford White BNTV-600 User Manual

Page 13: Table 3a - pvc vent terminal kits

Advertising
background image

Page 9

BRUTE ELITE

Method 1: Two permanent openings, one commencing within

12” (300mm) of the top and one commencing within 12”

(300mm) of the bottom, of the enclosure shall be provided.
The openings shall communicate directly, or by ducts, with
the outdoors or spaces that freely communicate with the
outdoors. When directly communicating with the outdoors, or
when communicating to the outdoors through vertical ducts,

each opening shall have a minimum free area of 1 square inch

per 4000 Btu/hr (550 square mm/kW) of total input rating
of all equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening shall

have a minimum free area of not less than 1 square inch per

2000 Btu/hr (1100 square mm/kW) of total input rating of all
equipment in the enclosure.

Method 2

: One permanent opening, commencing within

12” (300mm) of the top of the enclosure, shall be permitted.
The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct
to the outdoors or spaces that directly communicate with the

outdoors and shall have a minimum free area of 1 square inch

per 3000 Btu/hr (734 square mm/kW) of the total input rating
of all equipment located in the enclosure. This opening must
not be less than the sum of the areas of all vent connectors in

the confined space.

Section 3 -

VENTING AND COMBUSTION AIR

3.1 Combustion Air

Brute Elite boilers and water heaters must have provisions
for combustion and ventilation air in accordance with the
applicable requirements for Combustion Air Supply and

Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in

Canada, the Natural Gas and Propane Installation Code, CSA

B149.1. All applicable provisions of local building codes must
also be adhered to.

A Brute Elite unit can take combustion air from the space
in which it is installed, or the combustion air can be ducted
directly to the unit. Ventilation air must be provided in either
case.

Combustion Air From Room
In the United States, the most common requirements specify
that the space shall communicate with the outdoors in

accordance with method 1 or 2, which follow. Where ducts

are used, they shall be of the same cross-sectional area as the
free area of the openings to which they connect.

INSTALLATION STANDARDS

MATERIAL

UNITED STATES

CANADA

ABS

ANSI/ASTM D1527

PVC, sch 40

ANSI/ASTM D1785 or D2665

Air pipe material must be chosen

CPVC, sch 40

ANSI/ASTM F441

based upon the intended application of the boiler.

Single wall galv. steel

26 gauge

Table 4 - Required Combustion Air Pipe Material

PRO TECH (FasNSeal)

HEAT FAB (Saf-T-Vent)

Z FLEX (Z-Vent)

SIZE

Boiler

Flue

Intake Air

Boiler

Intermediate

Flue

Intake Air

Boiler

Flue

Intake Air

Adapter Termination

Termination Adapter Adapter Termination

Termination Adapter Termination

Termination

399-600

F303759

FSBS4

FSAIH04

KB285600 9454BUREZ-1* 9492 9414TERM 2SVSLA04 2SVSTP04 2SVSTEX0490

FSRC4(R.C)

303888

5400CI

2SVSRCX04

750-850

F303759 FSBS6 FSAIH04

303888

Table 3b - Approved Stainless Terminations and Adapters

HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS

2” PVC

3” PVC

4” PVC

6” PVC








Size

S

tandar

d

C

onc

ent

ri

c

C

A

0060

00

F

lus

h M

ount

C

A

0101

00

S

tandar

d

C

A

0059

00

C

onc

ent

ri

c

239

-44069

-01

F

lus

h M

ount

C

A

0101

01

S

tandar

d

F

lus

h M

ount

C

A

0101

02

S

tandar

d

80

incl.

opt.

opt.

opt.

opt.

opt.

n/a

n/a

n/a

105

incl.

opt.

opt.

opt.

opt.

opt.l

n/a

n/a

n/a

150

n/a

n/a

n/a

incl.

opt.

opt.

n/a

n/a

n/a

199/210

n/a

n/a

n/a

incl.

opt.

opt.

n/a

n/a

n/a

285

n/a

n/a

n/a

opt.

opt.

opt.

incl.

opt.

n/a

399

n/a

n/a

n/a

n/a

n/a

n/a

incl.

opt.

n/a

500

n/a

n/a

n/a

n/a

n/a

n/a

incl.

opt.

n/a

600

n/a

n/a

n/a

n/a

n/a

n/a

incl.

opt.

opt.

750

n/a

n/a

n/a

n/a

n/a

n/a

n/a

opt.

incl.

850

n/a

n/a

n/a

n/a

n/a

n/a

n/a

opt.

incl.

Concentric vent terminal = 10 ft. pipe length

Table 3a - PVC Vent Terminal Kits

Advertising
This manual is related to the following products: