Bradford White BNTV-600 User Manual

Page 77

Advertising
background image

Page 73

BRUTE ELITE

Name

PW?

Function

How to get there

Max. outdoor temp. (CH) -

Used with Outdoor Reset –
This is the maximum outdoor temperature at which

the Outdoor Reset feature will be active. Above

this point, the Low Water Temp. will be used as the

setpoint.

Quick Start
Info/ Advanced Setup/ CH

Configuration/ Outdoor Reset Config.

Max. outdoor temp. (LL) -

When using the Lead/ Lag system to control

multiple boilers, with Outdoor Reset enabled –
This is the maximum outdoor temperature at which

the Outdoor Reset feature will be active.

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Outdoor Reset

MB1 Modbus address

-

Allows for a specific address assignment for each

control in the system (1-8).

Info/ Advanced Setup/ System

Config./ System ID and Access

MB2 Modbus address

-

Allows for a specific address assignment for each

control in the system (1-8).

Info/ Advanced Setup/ System

Config./ System ID and Access

Min. boiler water temp.

(CH)

-

Used with Outdoor Reset –
If a value is entered here, the temperature in the

boiler will never be allowed to drop below this

temperature. This will protect the boiler against

possible damage due to expansion of ice inside

the unit. (Notice that this is different from the “Low

Water Temperature” described above.)

Info/ Advanced Setup/ CH

Configuration/ Outdoor Reset Config.

Min. outdoor temp. (CH) -

Used with Outdoor Reset –
This is the maximum outdoor temperature at which

the Outdoor Reset feature will be active. Below this

point, the system will use the normal CH setpoint.

Quick Start
Info/ Advanced Setup/ CH

Configuration/ Outdoor Reset Config.

Min. outdoor temp. (LL)

-

When using the Lead/ Lag system to control

multiple boilers, with Outdoor Reset enabled –
This is the maximum outdoor temperature at which

the Outdoor Reset feature will be active. Below this

point, the system will use the normal LL setpoint.

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Outdoor Reset

Min. water temp. (LL)

-

When using the Lead/ Lag system to control

multiple boilers, with Outdoor Reset enabled –
If a value is entered here, the temperature in the

boiler will never be allowed to drop below this

temperature. This will protect the boiler against

possible damage due to expansion of ice inside

the unit. (Notice that this is different from the “Low

Water Temperature” described above.)

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Outdoor Reset

Modbus address

-

When using the Lead/ Lag system to control

multiple boilers –
Each controller must have a unique Modbus

address.

Info/ Advanced Setup/ System

Config./ System ID and Access

Modulation sensor

-

Used with external modulation control –
The choices are Outlet/ Inlet/ S5, S10, and None.

Info/ Advanced Setup/ CH

Configuration

OEM ID

Y

Cannot be changed by the Installer.

Info/ Advanced Setup/ System

Config./ System ID and Access

OEM password

Y

Cannot be changed by the installer.

Info/ Advanced Setup/ System

Config./ System ID and Access

Off hysteresis (CH)

-

For hydronic heating (Central Heat) –
The control system will not shut off the boiler until

the temperature at the System sensor rises to the

CH setpoint plus a hysteresis value (normally about

10°F).

Info/ Advanced Setup/ CH

Configuration

Advertising