Bradford White BNTV-600 User Manual

Page 78

Advertising
background image

Page 74

B

RADFORD

W

HITE

C

ORP.

Name

PW?

Function

How to get there

Off hysteresis (DHW)

-

When producing Domestic Hot Water –
The control system will not shut off the boiler until

the temperature at the System sensor rises to the

DHW setpoint plus a hysteresis value (normally

about 10°F).

Info/ Advanced Setup/ DHW

Configuration

Off hysteresis (LL)

-

When using the Lead/ Lag system to control

multiple boilers –
The control system will not shut off the boilers until

the temperature at the System sensor rises to

the Lead/Lag CH setpoint plus a hysteresis value

(normally about 10°F).

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Master Config.

On hysteresis (CH)

-

For hydronic heating (Central Heat) –
The control system will not fire the boiler until the

temperature at the System sensor drops to the CH

setpoint minus a hysteresis value (normally about

10°F).

Info/ Advanced Setup/ CH

Configuration

On hysteresis (DHW)

-

When producing Domestic Hot Water –
The control system will not fire the boiler until the

temperature at the System sensor drops to the

DHW setpoint minus a hysteresis value (normally

about 10°F).

Info/ Advanced Setup/ DHW

Configuration

On hysteresis (LL)

-

When using the Lead/ Lag system to control

multiple boilers –
The control system will not fire the boilers until the

temperature at the System sensor drops to the

Lead/Lag CH setpoint minus a hysteresis value

(normally about 10°F).

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Master Config.

Outdoor reset (CH)

-

Enable = Outdoor Reset feature turned on

Quick Start
Info/ Advanced Setup/ CH

Configuration/ Outdoor Reset Config.

Outdoor reset enable

(LL)

-

When using the Lead/ Lag system to control

multiple boilers –
Enable = Outdoor Reset feature turned on

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Outdoor Reset

P gain (CH)

Y

This gain is applied to the Proportional term of the

PID equation for the hydronic (Central Heat) loop.

Info/ Advanced Setup/ CH

Configuration

P gain (DHW)

Y

This gain is applied to the Proportional term of the

PID equation for the Domestic Hot Water loop.

Info/ Advanced Setup/ DHW

Configuration

P gain (LL)

Y

When using the Lead/ Lag system to control

multiple boilers –
This gain is applied to the Proportional term of the

PID equation for the hydronic loop.

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Master Config.

Priority time

Y

If this parameter is non-zero, then a Domestic Hot

Water demand takes priority over other demand

sources for the specified time. The priority override

timing is reset when demand from the DHW source

turns off.

Info/ Advanced Setup/ DHW

Configuration

Priority vs Central Heat

Y

If a CH call and a DHW call arrive at the same time,

which has priority?

Info/ Advanced Setup/ DHW

Configuration

Priority vs Lead/Lag

Y

When using the Lead/ Lag system to control

multiple boilers –
If a call for hydronic heat and a DHW call arrive at

the same time, which has priority?

Info/ Advanced Setup/ DHW

Configuration