Hit Products Pro-Two User Manual

Page 5

Advertising
background image

WWW.RAINPROCO.COM

WWW.RAINPROCO.COM

PRO 2

3

Input Power:

100-230VAC 50/60Hz

Controller Surge Protection:

Surge protection is provided by circuit board components, and connection to a Ground-

ing Rod. Rod is customer supplied.

Field Surge Protection:

Is provided by the use of LP-SPD-F devices. Designed to be installed in valve boxes

every 200-300 feet or as needed and attached to a Grounding Rod. Grounding Rod is

customer supplied.

Field Wiring:

Wire type:

Single strand direct burial, Jacketed two conductor, or

Stranded.

Wire Size: Minimum 18 gauge

Wire Runs: Maximum 2000’

Branching &

Teeing:

T

T

Yes

DO NOT “Loop”

DO NOT “Loop”

the field wires back to the controller OR back onto themselves.

DO NOT splice and direct bury

DO NOT splice and direct bury

wire connections/splices. All wire connections/splices

should be made in valve boxes.

Maximum Valve Operation:

A maximum of 2 valves, any where on the system, may operate simultaneously, of either

same number or combinations of different numbers. The 2 valve maximum does not

include the Master valve or Pump Start Relay. Controller specifications are based on

a Standard 24VAC irrigation valve solenoid rated with a maximum 350 mA inrush and

a maximum 250 mA holding current at 24VAC. Controller is not compatible with Low

Power / Diode Bridge solenoids.

Wire Connectors:

One of the most critical installation requirements of a PRO 2 two wire system is the

quality of your wire connections. If you follow these directions you will have a reliable,

dependable control system for many years. It is suggested to solder all decoder (red

wire) connections to your main two-wire run. Install the soldered two-wire connection in

a waterproof underground connector housing. When soldering is impractical, a water-

proof “dry-type” Hit Products DBC-BR wire connector is required. The above mentioned

product will provide an uncontaminated, reliable dry connection.

A DBC-BR Kit (1 each) is included with each Pro 2 Decoder.

Do not use pre-filled wire nut connectors as they will impede the transfer of the

Do not use pre-filled wire nut connectors as they will impede the transfer of the

signal through the wire splice.

signal through the wire splice.