Stop/hold button, Safety check, Check safety timings – Beckett 7590 Gas Power Burner Control User Manual

Page 10: Check for normal operation

Advertising
background image

10

supply system using a soap and water

solution or electronic detection.

Check Safety Timings

Turn off gas supply to appliance.

Restore power to the appliance.

Turn the thermostat or controller up

to call for heat. Status LED should be

powered. Motor should start.

Following pre-purge, the control will

energize the separate igniter, spark

should be present at the burner head.

MV LED should light and gas valve

should open.

Spark should stay on for the entire

ignition timing.

Spark should switch off at the end of the

ignition timing. Gas valve and MV LED

should turn off.

If the control is programmed for single

trial for ignition, the Status LED will flash

rapidly to indicate lockout.

For controls programmed for multiple

trials for ignition, allow the control to

continue retrials until lockout occurs.

Status LED will flash slowly during

waiting period between ignition cycles.

Check for Normal Operation

Restore power to the appliance.

If control is in lockout push Status/Reset

button.

Turn manual gas cock to on position.

Turn gas valve to on position using either

the manual gas knob or the electrical

switch on the valve.

Turn the thermostat or controller up to

call for heat. Status LED should be

powered. Motor should start.

Following pre-purge, the igniter will be

turned on and spark should be present

at the burner head. The MV LED should

turn on and the gas valve should open.

Motor continues running.

When the burner is lit by spark, ignition

The 7590D and T models can be configured

to automatically allow an ignition retry

once every 1-8 hours (selectable using the

diagnostic tool or by factory configuration).

This configuration may help by allowing

periodic ignition retries until the gas supply

is restored. The ignition retries will only

happen if there is power to the burner and

there is a call for heat from the thermostat or

controller. The control will not allow retry if

the lockout was caused by a failed gas valve

relay check. This retrial feature may not be

available (factory locked) in some controls

including the 7590C version.

If the red Status/Reset button is flashing

slowly (1 time per second) and the motor/

blower is off, the control is waiting for retrial.

When the standard control (7590D and T) is

in the waiting period, it can only be reset by

removing power from the control.

Stop/Hold Button

Holding the Status/Reset button down for

more than 1 second will interrupt the ignition

sequence. The control will enter a hold

mode and all control functions will stop.

When the Status/Reset button is released,

the control will start the ignition sequence

over (including pre-purge).

Safety Check

Before starting appliance, make sure that

all wiring is correct and secure. Repair or

replace any loose connections or damaged

wire. Use only wire rated for the application.

Use UL approved wire of the gauge

and temperature rating specified by the

appliance or burner manufacturer for any

replacement wiring.

Use UL approved solid conductor ignition

cable. Cable must meet the temperature

and voltage ratings specified by the

manufacturer. Use insulated boots or

terminals, if needed, to prevent sparking

to burner parts.

Perform a visual

inspection of all system

components including the gas supply

system. Check for any leaks in the gas

Advertising