GeniSys Gas Power Burner Control Installation and Operation Manual

▪ Flame is not being proven, control will lockout or enter waiting period.

▪ With power off, check the electrical connections from the control to

the flame rod.

▪ Make sure all connections are clean and free of corrosion or build up.

▪ Check the continuity of the ground wire and the sense wire.

▪ The control, electrode and flame sensor must have a common ground

with the burner for proper operation.

▪ Check the ceramic on the flame rod for any chips or cracks, replace

if needed.

▪ Check the flame rod for build up and clean or replace if needed.

▪ Make sure the electrode and flame rod are covered with a steady,

stable flame, adjust flame rod or electrode if needed.

▪ Restore power, if flame is still not being proven, replace the control.

Is the yellow

Flame LED on?

Normal run mode

Note: If Flame LED is flashing slowly,

follow these same steps to improve

flame signal strength and reliability.

▪ When the burner lights successfully, turn the thermostat or controller off to end the call for heat.

▪ The burner should go out quickly. All LEDs on the control should go out.

▪ If the burner remains lit for more than a few seconds, and the MV LED is out, replace the gas valve.

▪ If the LEDs remain lit, check the thermostat or controller for proper operation.

▪ Repeat the ignition sequence several times to make sure the system is operating properly.