Simplified sequence of operation, The burner should turn off quickly, Reference table 2 ) – Beckett 7590 Gas Power Burner Control User Manual

Page 11: Call for heat, status led is turned on, Control performs safe-start check, If safe-start fails, control locks out

Advertising
background image

11

GeniSys Gas Power Burner Control Installation and Operation Manual

will shut off and the main gas valve will

remain open.

Multiple ignition trials may be needed to

establish gas flow on new installations or

if burner has been out of use. If control

locks out, push Status/Reset button to

restart ignition sequence.

When the burner lights, the Flame LED

should be on continuously.

Check burner for proper combustion per

burner or appliance instructions.

Remove call for heat by turning the

thermostat or controller down.

The MV LED, Flame LED and Status

LED should go off. The valve should

close. Motor should turn off.

The burner should turn off quickly.

Simplified Sequence of Operation

(Reference

Table 2)

Call for heat, Status LED is turned on.

Control performs safe-start check

If safe-start fails, control locks out.

If safe-start passes, control checks for

presence of flame.

If flame is present, control will enter hold

state until flame is no longer present.

Flame LED and Status LED will flash

until flame is no longer present.

If flame is not present, control will check

status of air proving switch. If switch is

closed, (indicating the pressure switch is

stuck) control will enter lockout.

If the air proving switch is open, the

motor will start. Once the air proving

switch closes, pre-purge will begin

(lasting 1-240 seconds). Pre-purge or

ignition timings will not start until the air

proving switch closes.

The air proving switch must close to

prove combustion air is present. If switch

fails to close during the specified period,

the control will enter lockout.

When pre-purge is completed, the control

turns on the igniter and the gas valve.

MV LED will turn on.

Spark continues until end of ignition

timing or until flame is proved.

Once flame is proved, The Flame LED is

turned on and the spark is turned off. The

gas valve and MV LED remain energized.

If flame is not proved, the control will

lockout or enter the inter-trial waiting

period. Status LED will flash rapidly for

lockout or slowly for inter-trial waiting.

If multiple trial logic is used, the control

will complete the trials for ignition

When flame is proved the control will

continue in run mode until the end of

the call for heat.

When the call for heat is ended, the

gas valve, MV LED, Flame LED, Status

LED and motor turn off.

Table 2 - Operating Sequence

LEDs

Call for Heat

FLAME

MV

STATUS

Status LED

turns on

Motor Start

FLAME

MV

STATUS

Status LED

ON

Pre-purge

FLAME

MV

STATUS

Status LED

Flashes

Ignition

FLAME

MV

STATUS

Status, MV

LEDs On

Run

FLAME

MV

STATUS

Status, MV,

Flame LEDs On

End Call for Heat

FLAME

MV

STATUS

LEDs Off

Timers &

Timings

Pre-purge Timer

1 - 240 Seconds

Ignition Trial

Timer

4 - 15 Seconds

Flame Check

On

On

On

On

On

Motor/Blower

Blower Starts

On

On

On

Off

Air Switch Check

On

Air Switch Closes

On

On

On

Igniter

On

Off

Off

Gas Valve

On

On

Off