Specifications, Electrical ratings, Electrical connections – Beckett 7590 Gas Power Burner Control User Manual

Page 4: Environmental ratings, Approvals, Lockout sequence options, Timings, Control cycling rate, 4environmental ratings, Additional features

Advertising
background image

4

Environmental Ratings

Operating Temperature Range: -40°F

to +175°F (-40°C to +79.4°C).

Relative Humidity Operating Range 5%

- 95% (non-condensing).

Not intended for outdoor use unless

mounted in appropriate enclosure.

Approvals

ETL listed per ANSI Z21.20 and CSA

C22.2#199

Lockout Sequence Options

Sequence is usually factory selected

Lockout after single try for ignition

Lockout with retrial every 1-8 hours

Lockout after 3 trials for ignition

Manual Reset logic: shutdown after

failure to light during trial for ignition

timing or after flame failure, (no relight

attempt), after 5 minute minimum

waiting time, 1 retry attempt allowed,

then non-volatile lockout. Lockout

must be manually reset.

Timings

All timings can be factory locked.

Timings below may be field selectable

on some models.

Ignition Timing: 4-15 seconds (4

seconds if Manual Reset)

Pre-purge timing: 1-240 seconds

Inter-purge timing: 90-300 seconds

Control Cycling Rate

The 7590 is designed for use in typical

heating applications which cycle a

few times per hour during the heating

season. More rapid cycling of the control

will shorten the useful life of the control.

Controls in rapid cycling applications

should be checked monthly for proper

operation. All controls should be checked

at least annually for proper operation.

Specifications

Electrical Ratings

Voltage: 120 volts 50/60 Hz (igniter,

motor) 24 volts (18-30 Vac) 50/60Hz

(gas valve and air proving switch)

Current Draw (run): 0.2

Amps (control

only)

Main Valve Rating: 2.0 Amps

Motor Relay Rating: 7.4 Amps (120V)

Igniter Relay Rating: 1.0 Amp (120V)

Minimum Flame Current Required:

1.0 µA

Flame Failure Response Time: 0.8

Seconds (Max.)

Control is not polarity sensitive

Heat Anticipator Setting: 0.2 amp + gas

valve current draw

Electrical Connections

Two T-T screw terminals (on top) (see

Figure 1)

1/4” Quick Connects (6 total on bottom)

Igniter, L2

Motor, L2

L1, L2

3/16” Remote Sense quick connect

terminal (on bottom)

6-Pin (24V) connector (on bottom)

24 Volt Input, Gas Valve, Burner

Ground

2-Pin (24 V) connector (on bottom)

Air Pressure Switch

Micro-USB Communications Port (on

side of control) for diagnostic tool and

alarm module (COM1).

Additional Features

3 Diagnostic LEDs; Status (red), Flame

(yellow), MV (green)

Alarm Contacts (optional module)