Features – Beckett 7590 Gas Power Burner Control User Manual

Page 3

Advertising
background image

3

GeniSys Gas Power Burner Control Installation and Operation Manual

Table 1 - Ignition Model Numbers

Model Line Model Description

Part Number

Feature

120 volt Igniter and blower motor

output

24 volt gas valve

output

2 Pin- connector

for

pressure switch

Non-volatile

lockout*

Gas Power

Burner

Standard

7590DYYYY

X

X

X

No Pressure Switch

7590TYYYY

X

X

Non-volatile Manual

Reset

7590CYYYY

X

X

X

X

The standard model 7590 is designed for use on applications below 400,000 BTUs. For

applications above 400,000 BTUs, contact Beckett’s Engineering Group.

*Non-volatile lockout cannot be cleared by removing power from the control. The

control must be reset by pressing the Status/Reset button when the control is powered.

Features

For use in Natural Gas or LP gas applications.

Controls 120 Vac spark igniter, motor/blower and 24 Vac gas valve, 50/60 HZ

Provides proof of flame through flame rectification using a separate flame rod

Checks combustion air proving switch contacts (24 Vac) on 7590C and 7590D

models to prove moving combustion air and guard against welded contacts.

Field selectable for either lockout or recycle on loss of combustion air

Field selectable relight or recycle operation on loss of flame (may be factory locked)

Field selectable single or multiple trials for ignition on some models (may be locked)

Field selectable ignition timing on some models (may be factory locked)

Field selectable pre-purge timing (may be factory locked)

The microprocessor is checked for proper operation prior to each ignition cycle

Check for welded valve relays on each cycle

Mounts on standard 4 x 4 junction box

3 status LEDs supply basic diagnostics, additional diagnostic information and field

configuration will be available through a separate diagnostic tool

An optional separate alarm module provides alarm contacts (dry contacts)

A reset button is standard on all controls, non-volatile manual reset logic is available

on specific models (7590C).

Communication Port to connect diagnostic tool and alarm module

Advertising