Troubleshooting sequence – Beckett 7590 Gas Power Burner Control User Manual

Page 15

Advertising
background image

15

GeniSys Gas Power Burner Control Installation and Operation Manual

▪ No power to the module.

▪ Check to make sure thermostat or controller is calling for

heat and limit is closed.

▪ See instructions in troubleshooting box “If the red Status

LED is off”.

Is the red

Status LED on?

Pre-Purge

Troubleshooting Sequence

Start with gas supply off and set thermostat or controller to call for heat.

Continued on

next page

YES

NO

FLAME

MV

STATUS

FLAME

MV

STATUS

▪ If red Status LED is flashing slowly (1 time per second)

control is in pre-purge, motor should be running.

▪ If red Status LED is flashing quickly (3 times per second)

control is in lockout. Check the air pressure switch and

follow steps under troubleshooting box “If the red Status LED

is flashing quickly”.

▪ If red Status LED is on steadily, the control is waiting for the

air pressure switch. See instructions “If the red Status LED

is on steadily”.

▪ If both Status and MV LEDs are lit, control is in trial for

ignition, the igniter should be sparking and motor running.

▪ Check incoming line voltage to burner and control (120 V)

▪ With power off, check all wiring and connections to igniter.

▪ Check for correct spark gap on ignition electrode.

▪ Check ignition cable and ground wire for continuity, replace

if necessary.

▪ If ignition cable shows signs of melting or wear, replace and

reroute or shield cable.

▪ Check ceramic insulator around the electrode for cracking

or chipping, replace if needed.

▪ With power off, loosen 7590 from junction box, carefully

remove female quick connect terminals from Igniter and L2

male terminals. Restore power and start ignition sequence.

With the Status and MV LEDs on, carefully measure the

voltage between male Igniter and L2 terminals. Voltage

should be 120 Vac. If no voltage, replace control.

▪ If voltage between Igniter and L2 terminals is 120 volts and

all connections to igniter, electrode and ground are good,

replace igniter.

▪ Status LED will flash approximately once per second during

pre-purge. Burner motor should be running.

▪ Wait for the control to complete the pre-purge timing.

Note: Status LED does not flash for a 1 second pre-purge.

Trial for Ignition

Is the igniter

sparking during

trial for ignition?

Pre-purge

complete?

1-240 sec.

NO

YES

NO

YES

FLAME

MV

STATUS