Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

Page 110 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

IGN SWTCH CLOSED

DURING PURGE

1.

Air/Fuel Valve not rotating.

2.

Defective or shorted switch.


3.

Switch wired incorrectly.

4.

Defective Power Supply Board

or fuse.

5.

Defective IGST Board.

1.

Start the unit. The Air/Fuel Valve should rotate to the purge

(open) position. If the valve does not rotate at all or does

not rotate fully open, check the Air/Fuel Valve calibration.

If calibration is okay, the problem may be in the Air-Fuel

Valve or the Control Box. Refer to qualified service

personnel.

2.

If the Air/Fuel Valve does rotate to purge, check the ignition

switch for continuity between the N.O. and COM terminals.

If the switch shows continuity when not in contact with the

cam replace the switch.

3.

Check to ensure that the switch is wired correctly (correct

wire numbers on the normally open terminals). If the switch

is wired correctly, replace the switch.

4.

Check DS1 & DS2 LEDs on Power Supply Board. If they

are not steady ON, replace Power Supply Board.

5.

Check “Heartbeat” LED DS1 and verify it is blinking ON &

OFF every second. If not, replace IGST Board.

IGN SWTCH OPEN

DURING IGNITION

1.

Air/Fuel Valve not rotating to

ignition position.

2.

Defective ignition switch.

3.

Defective Power Supply Board

or fuse.

4.

Defective IGST Board.

1.

Start the unit. The Air/Fuel Valve should rotate to the purge

(open) position, then back to ignition position (towards

closed) during the ignition cycle. If the valve does not rotate

back to the ignition position, check the Air/Fuel Valve

calibration. If calibration is okay, the problem may be in the

Air/Fuel Valve or the Control Box. Refer fault to qualified

service personnel.

2.

If the Air/Fuel Valve does rotate to the ignition position,

check the ignition position switch for continuity between the

N.O. and COM terminals when in contact with the cam.

3.

Check DS1 & DS2 LEDs on Power Supply Board. If they

are not steady ON, replace Power Supply Board.

4.

Check “Heartbeat” LED DS1 and verify it is blinking ON &

OFF every second. If not, replace IGST Board.