AERCO BMK 2000DF User Manual

Page 113

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 113 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

RECIRC PUMP FAILURE

1.

Internal recirculation pump failed.

1. Replace recirculation pump.

REMOTE SETPT

SIGNAL FAULT

1.

Remote setpoint signal not present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

2.

Signal is not isolated (floating) if 4

to 20 mA.

3.

Control Box signal type selection

switches not set for correct signal

type (voltage or current).

1.

Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and unit.

2.

Check signal at source to ensure it is isolated.

3.

Check DIP switch on PMC board to ensure it is set correctly for the

type of signal being sent. Check control signal type set in

Configuration Menu.

RESIDUAL

FLAME

1.

Defective Flame Detector.

2.

SSOV not fully closed.

1.

Replace Flame Detector.

2.

Check open/close indicator window of Safety Shut-Off Valve (SSOV)

and ensure that the SSOV is fully closed. If not fully closed, replace

the valve and or actuator.
Close the 2” Gas Shut-Off Valve downstream of SSOV (Figure 2-7).

Install a manometer or gauge at the leak detection port between the

SSOV and Gas Shut Off Valve. If a gas pressure reading is observed

replace the SSOV Valve and/or Actuator.

SSOV FAULT DURING

PURGE

See SSOV SWITCH OPEN

SSOV FAULT

DURING RUN

SSOV switch closed for 15 seconds

during run.

1.

Replace or adjust micro-switch in SSOV actuator. If fault persists,

replace actuator.

SSOV RELAY

FAILURE

1.

SSOV relay failed on IGST board.

2.

Floating Neutral.

3.

Hot and Neutral reversed at SSOV.

1.

Press CLEAR button and restart unit. If fault persists, replace

Ignition/Stepper (IGST) Board.

2.

The Neutral and Earth Ground are not connected at the source and

therefore there is a voltage measured between the two. Normally this

measurement should be near zero or no more than a few millivolts.

3.

Check SSOV power wiring.

Advertising
This manual is related to the following products: