2 acs setup and startup, 7 combination control system (ccs) – AERCO BMK 2000DF User Manual

Page 74

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 5 – MODE OF OPERATION

Page 74 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

5.6.2 ACS Setup and Startup

This mode of operation is factory preset and the ACS controls the firing rate (air/fuel valve %

open position). There are no setup instructions for each individual unit.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go

off and the MANUAL LED will light
To change back to the ACS mode, simply press the AUTO/MAN switch. The REMOTE LED will

again light and the MANUAL LED will go off.

5.7 COMBINATION CONTROL SYSTEM (CCS)

NOTE

Only ACS can be utilized for the Combination Control System.

A Combination Control System (CCS) is one that uses multiple boilers to cover both space-

heating and domestic hot water needs. The theory behind this type of system is that the

maximum space-heating load and the maximum domestic hot water load do not occur

simultaneously. Therefore, boilers used for domestic hot water are capable of switching

between constant setpoint and ACS control.
For a typical CCS, an adequate number of boilers are installed to cover the space-heating load

on the design-day. However, one or more units are used for the domestic hot water load as well.

These boilers are the combination units and are referred to as the combo boilers. The combo

boilers heat water to a constant setpoint temperature. That water is then circulated through a

heat exchanger in a domestic hot water storage tank.
Only the AERCO Control System (ACS) is necessary to configure this system if only a single

valve is used to switch from space heating to domestic hot water. However, the ACS Relay

Panel is required in combination with the ACS when there are up to two isolation valves, boiler

interlocks, and/or a Domestic Hot Water (DHW) pump in a Combination heating plant where

AERCO boilers are being used for both Building Heat and Domestic Hot Water heating.
The following two options are available for using a combination system; one that uses only the

ACS, and one that requires the optional ACS Relay Box:

OPTION 1 - This option is selected when the ACS controls a boiler plant containing up to

eight combination boilers that are Domestic Hot Water Priority (DHW PRIORITY) boilers,

along with building heat (BLDG HEAT) boilers, and one hydronic isolation valve in the main

header between the BLDG HEAT boilers and the DHW PRIORITY boilers.

OPTION 2 – When this option is selected, the ACS Relay Panel must be used in

conjunction with the ACS. For this option, the ACS controls a boiler plant containing up to

eight combination boilers that are divided up into Building Priority (BLDG PRIORITY)

boilers and Domestic Hot Water Priority (DHW PRIORITY) boilers, along with building heat

(BLDG HEAT) boilers, and using two hydronic isolation valves in the main header, one

between the BLDG HEAT and BLDG PRIORITY boilers, and the other between the BLDG

PRIORITY and the DHW PRIORITY boilers.

In Option 2, when the space-heating load is such that when all the space-heating boilers are at

the 100% valve position, the ACS will then ask the ACS Relay Box for the domestic boilers to

become space-heating boilers. Provided the domestic hot water load is satisfied, the combo (hot

water) boilers will then become space-heating boilers. If the domestic hot water load is not

satisfied, the combo boiler(s) remain on the domestic hot water load. If the combo boilers switch

over to space heating, but there is a call for domestic hot water, the ACS Relay Box switches

the combo units back to the domestic load. The ACS in combination with the ACS Relay Box

Advertising
This manual is related to the following products: