Chapter 5. mode of operation, 1 introduction, 2 indoor/outdoor reset mode – AERCO BMK 2000DF User Manual

Page 69: 1 reset ratio, 2 building reference temperature, 3 outdoor air temperature sensor installation, 4 indoor/outdoor startup, Chapter 5, Mode of operation

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 5 – MODE OF OPERATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 69 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

CHAPTER 5. MODE OF OPERATION

5.1 INTRODUCTION

The boiler is capable of being operated in any one of six different modes. The following sections

in this Chapter provide descriptions of each of these operating modes. Each boiler is shipped

from the factory tested and configured for the ordered mode of operation. All temperature

related parameters are at their factory default values which work well in most applications.

However, it may be necessary to change certain parameters to customize the unit to the system

environment. A complete listing and descriptions of the temperature related parameters are

included in Appendix A. Factory defaults are listed in Appendix D. After reading this chapter,

parameters can be customized to suit the needs of the specific application.

5.2 INDOOR/OUTDOOR RESET MODE

This mode of operation is based on outside air temperatures. As the outside air temperature

decreases, the supply header temperature will increase and vice versa. For this mode, it is

necessary to install an outside air sensor as well as select a building reference temperature and

a reset ratio.

5.2.1 Reset Ratio

Reset ratio is an adjustable number from 0.1 to 9.9. Once adjusted, the supply header

temperature will increase by that number for each degree that the outside air temperature

decreases. For instance, if a reset ratio of 1.6 is used, for each degree that outside air

temperature decreases the supply header temperature will increase by 1.6 degrees.

5.2.2 Building Reference Temperature

This is a temperature from 40°F to 230°F. Once selected, it is the temperature that the system

references to begin increasing its temperature. For instance, if a reset ratio of 1.6 is used, and

we select a building reference temperature of 70°F, then at an outside temperature of 69°F, the

supply header temperature will increase by 1.6° to 71.6°F.

5.2.3 Outdoor Air Temperature Sensor Installation

The outdoor air temperature sensor must be mounted on the North side of the building in an

area where the average outside air temperature is expected. The sensor must be shielded from

the sun's direct rays, as well as direct impingement by the elements. If a cover or shield is used,

it must allow free air circulation. The sensor may be mounted up to two hundred feet from the

unit. Sensor connections are made at the Input/Output (I/O) Box on the front of the boiler.

Connections are made at the terminals labeled OUTDOOR AIR IN and AIR SENSOR COM

inside the I/O Box. Use shielded 18 to 22 AWG wire for connections. A wiring diagram is

provided on the cover of the I/O Box. Refer to Chapter 2, section 2.9.1 for additional wiring

information.

5.2.4 Indoor/Outdoor Startup

Startup in the Indoor/Outdoor Reset Mode is accomplished as follows:

NOTE

A design engineer typically provides design outdoor air

temperature and supply header temperature data

Advertising
This manual is related to the following products: