CHAPTER 8 – TROUBLESHOOTING GUIDE

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 115 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES

Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.

TABLE 8-2: BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED

OBSERVED INCIDENT

PROBABLE CAUSES

CORRECTIVE ACTION

Hard Light-Off

1.

Clogged/damaged Gas Injector

on Igniter-Injector (Figure 8-1).

2.

Defective Staged Ignition

Solenoid (Figure 8-1).

1.

Disconnect the Staged Ignition Assembly solenoid from

the Gas injector Tube of the Igniter-Injector (Figure 8-1)

and inspect Gas Injector to ensure it is not clogged or

damaged.

2.

Close the 2” Manual Shutoff Valve. Attempt to start the unit

and listen for a “clicking” sound that the Staged Ignition

Solenoid makes during Ignition Trial. If “clicking” sound is

not heard after 2 or 3 attempts, replace the Staged Ignition

Solenoid.

Fluctuating Gas Pressure

1.

Gas pressure going into unit is

fluctuating.

2.

Damping Orifice not installed.

1.

Stabilize gas pressure going into unit. If necessary,

troubleshoot Building Supply Regulator.

2.

Check to ensure that the Damping Orifice is installed in the

SSOV Actuator shown in Figure 8-2. (For IRI (DBB) Gas

Trains, the Damping Orifice is installed in the downstream

SSOV Actuator).

Air/Fuel Valve “hunting” at

the 80% Valve Position

1.

IGST and Power Supply Boards

in Control Box are outdated.

1.

Check to ensure that the IGST and Power Supply Boards

are Rev. E or higher.