Do not apply insulation to the top of the water heater, as this

will interfere with safe operation of the draft hood.

Do not cover the outer door, thermostat or temperature &

pressure relief valve.

Do not allow insulation to come within 2” (50.8 mm) of the

floor to prevent blockage of combustion airflow to the burner.

Do not cover the instruction manual. Keep it on the side of

the water heater or nearby for future reference.

Do obtain new warning and instruction labels from Sears for

placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain

it does not sag, thereby obstructing combustion air flow.

Combustion Air and Ventilation for
Appliances Located in Unconfined Spaces

UNCONFINED SPACE

Is space whose volume is not less than

50 cubic feet per 1,000 Btu per hour (4.8 m^ per kW) of the

aggregate input rating of all appliances installed in that space.

Rooms communicating directly with the space in which the

appliances are installed, through openings not furnished with

doors, are considered a part of the unconfined space.

In unconfined spaces in buildings, infiltration may be adequate

to provide air for combustion, ventilation and dilution of flue

gases. However, in buildings of tight construction (for example,

weather stripping, heavily insulated, caulked, vapor barrier, etc.),

additional air may need to be provided using the methods

described in

Combustion Air and Ventilation for Appliances

Located in Confined Spaces.

Combustion Air and Ventilation for
Appliances Located in Confined Spaces

CONFINED

SPACE

is a space whose volume is less than

50 cubic feet per 1,000 Btu per hour (4.8 m^ per kW) of the

aggregate input rating of all appliances installed in that space,

A. ALL AIR FROM INSIDE BUILDINGS;

(See Figure 9 on page 9 and Figure 10 below)

The

confined

space

shall

be

provided

with

two

permanent

openings

communicating

directly

with

an

additional

room(s)

of sufficient volume so that the combined volume of all spaces

meets the criteria for an unconfined space. The total input of

all gas utilization equipment installed in the combined space

shall

be

considered

in

making

this

determination.

Each

opening shall have a minimum free area of one square Inch

per 1,000 Btu per hour (22 cm^/kW) of the total input rating of

all gas utilization equipment in the confined space, but not

less than 100 square inches (645 cm^). One opening shall

commence within 12 inches (30 cm) of the top and one

commencing within 12 inches (30 cm) of the bottom of the

enclosures.

FIGURE 10.

B. ALL AIR FROM OUTDOORS:

(See Figures 9, 11,12and 13)

The

confined

space

shall

be

provided

with

two

permanent

openings, one commencing within 12 inches (30 cm) of the top

and one commencing within 12 inches (30 cm) from the bottom

of the enclosure. The openings shall communicate directly, or

by ducts, with the outdoors or spaces (crawl or attic) that freely

communicate with the outdoors.

CHIMNEY OR

GAS VENT .

VENTILATION LOUVERS

(EACH END OF ATTIC)

WATER HEATER

FURNACE

INLET AIR DUCT

ALT. INLET AIR VENTILATION LOUVERS

FIGURE 11.

When directly communicating with the outdoors, each opening

shall have a minimum free area of 1 square inch per 4,000 Btu per

hour (5.5 cm^/kW) of total input rating of all equipment in the

enclosure. See Figure 12.

When

communicating

with

the

outdoors

through

vertical

ducts, each opening shall have a minimum free area of

1 square inch per 4,000 BTU per hour (5.5 cm^/kW) of total

input

rating

of

all

equipment

in

the

enclosure.

See

Figure 12.

11