Temperature-pressure relief valve, Temperature pressure relief valve -14, Caution – Kenmore 153.33443 User Manual

Page 14: Adanger, Arning, Explosion hazard, Water damage hazard

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Fit T & P valve insulation over valve. Make sure that the insulation

does not interfere with the lever of the T & P valve.

Secure all insulation using tape.

Temperature-Pressure Relief Valve

▲W

arning

Explosion Hazard

Temperature-pressure relief valve

must comply with ANSI Z2122

and ASME code.

Property

sized

temperature-

pressure relief valve must be
installed in opening provided.

Can result in overheating and
excessive tank pressure

Can cause serious injury or death.

This heater is provided with a properly certified combination

temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory

that

maintains

periodic

inspection

of

production

of

listed

equipment as meeting the requirements for Relief Valves and

Automatic Gas Shutoff Devices for Hot Water Supply Systems,
ANSI Z21.22 and the code requirements of ASME.

If replaced, the valve must meet the requirements of local

codes,

but

not

less

than

a

combination

temperature

and

pressure

relief

valve

certified

as

indicated

in

the

above

paragraph.

The valve must be marked with a maximum set pressure not
to

exceed

the

marked

hydrostatic

working

pressure

of

the

water heater (150 psi = 1,035 kPa) and a discharge capacity

not less than the water heater input rate as shown on the

model rating plate.

For safe operation of the water heater, the relief valve must not

be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designed for the relief valve.

Position the valve downward and provide tubing so that any

discharge will exit only within 6 Inches (153 mm) above, or at

any distance below the structural floor, see Figure 16. Be certain
that no contact is made with any live electrical part. The

discharge opening must not be blocked or reduced in size under
any

circumstances.

Excessive

length,

over

30

feet

(9.14 m), or use of more than four elbows can cause restriction

and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief

vaive and the tank. Do not connect tubing directly to discharge

drain unless a 6 inch air gap is provided. To prevent bodily

injury, hazard to life, or property damage, the relief valve must

be allowed to discharge water in quantities should circumstances

demand. If the discharge pipe is not connected to a drain or
other

suitable

means,

the

water

flow

may

cause

property

damage.

FIGURE 16.

CAUTION

Water Damage Hazard

■ Temperature-pressure relief valve discharge

pipe must terminate at adequate drain.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.

• Shall be of material listed for hot water distribution.

” Shall be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge

pipe.

• Shall terminate at an adequate drain.

• Shall not have any valve between the relief valve and tank.

ADANGER

Water

temperature

over

125°F

(52°C)

can

cause

severe

burns

instantly resulting in severe injury
or death.

Children,

the

elderly,

and

the

physically

or

mentally

disabled

are at highest riskfor scald injury.

Feel

water

before

bathing

or

showering.

Temperature

limiting

valves

are

available.

Read instruction manual for safe

temperaturesetting.

14

Advertising
This manual is related to the following products:

153, 334, 530