Facts to consider about the location (cont’d), A warning, Combustion air and ventilation – Kenmore THE ECONOMIZER 153.33298 User Manual

Page 10: Venting clearances, Awarning, Venting clearances ,11, Installation instructions (cont’d)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cont’d)

Facts to Consider About the
Location (cont’d)

A WARNING

This water heater must not be installed directly on carpeting.
Carpeting must be protected by a metal or wood panel

beneath the appliance extending beyond the full width and

depth of the appliance by at least 3 inches (76.2mm) in any
direction, or if the appliance is installed in an alcove or closet,
the entire floor must be covered by the panel. Failure to heed
this warning may result in a fire hi^ard.

A WARNING

Minimum clearances between the water heater and com­
bustible construction are 0" at the sides and rear, 5" at the

front, and 0" from the vent pipe. Clearance from the top of
the jacket is 12". Provide 24 inches front clearance for servic­

ing and adequate clearance between the jacket top & ceiling

for servicing the flue area. (See Figure I), Refer to the label
on the water heater adjacent to the gas control valve for all
clearances.

VcNTlIATlON

AIR

OPENINGS

1100 ir-^.

ZO" MIN.

12" WAX.

TOP VIEV/

OF CLOSET

WOhOLJT OOOP

RECTANGULAR

AIR DUCT

Figure 1

AIR r>i;ci

MIN.

Combustion Air and Ventilation

When determining the installation location for a power vent
water heater, snow accumulation and drifting should be consid­
ered in areas where applicable.

VENTING CLEARANCES

0" clearance for 3” (and optional 2") PVC, ABS or CPVC

Schedule 40 vent piping from combustible surfaces.

• 12" minimum from the ground, 9" ceiling overhangs. Figure 2.

• The Power Vent outlet terminal shall terminate at least 36"

above any forced air inlet located within 10 feet. Figure 3a.

• The Power Vent outlet terminal shall terminate at least 4 feet

below, 4 feet horizontally from or 1 foot above any door, win­
dow or gravity air inlet into the building. Figure 3a.

• 18" minimum in all directions from any obstruction that may

interfere. Figure 3b.

18" minimum from other natural draft (gravity) direct vent,

power vent or power direct vent appliance inlet and/or outlet
vent(s) when directly above or 135° to either side of center line.
Figure 3 c.

• 24" minimum from any appliance inlet and/or outlet vents when

directly below or 45“ to either side of center line. Figure 3c.

• The location selection must provide clearances for servicing

and proper operation of the water heater. Figure 4.

• Vent termination must not be within 4 feet of any items such

as gas meters, gas valves or other gas regulating equipment.

The venting system must be installed in a manner which

allows inspection of the installation of the vendng pipes and

joints as well as periodic inspection after installation as

required by ANSI Standards.

A WARNING

A gas water heater cannot operate properly without the cor­

rect amount of air for combustion. Do not install in a con­

fined area such a closet, unless you provide air as shown in
the "Facts to Consider About the Location” section. Never
obstruct the flow of ventilation air. If you have any doubts or
questions at ail, call your gas company. Failure to provide the

proper amount of combustion air can result in a fire or explo­

sion and can cause DEATH, SERIOUS BODILY INJURY, OR

PROPERTY DAMAGE.

AWARNING

If this water heater will be used In beauty shops, barber

shops, cleaning establishments, or self-service laundries
with dry cleaning equipment, it is imperative that the
water heater or water heaters be installed so that combus­
tion and ventilation air be taken from outside these areas.

Refer to the "Facts to Consider About the Location” sec­

tion of this manual and also the current edition of the

National Fuel Gas Code, ANSI Z223.1, also referred to as
NFPA 54 for specifics provided concerning air required.

AWARNING

Vent tennination must not be within 4 feet of any items such zs
gas meters, gas valves or other gas regulating equipment.

AWARNING

Failure to have required clearances between water heater and

combustible materiid will result in a fire hi^rd.

Figure 2

9" min, from

any overhang

Ç of Ffue

10

Advertising
This manual is related to the following products: