Installation instructions (cont’d) – Kenmore THE ECONOMIZER 153.33298 User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

1. when directly coinrnunicating with the outdoors, each opening

shall have a minimum free area of 1 square inch per 4,000 BTU
per hour of total input rating of all equipment in the enclosure.

(See Figure 7.)

2. When communicating with the outdoors through vertical ducts,

each opening shall have a minimum free area of 1 square inch
per 4,000 BTU per hour of total input rating of ail equipment
in the enclosure. (See Figure 8.)

Combustion Air and Ventilation

for Appliances Located in

Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all appli­
ances installed in that space. Rooms communicating directly with the
space in which the appliances are installed, through openings not fur­

nished with doors, are considered a part of the unconfined space,
in unconfined spaces in buildings, infiltration may be adequate to

provide air for combustion, ventilation and dilution of flue gases.

However, in buildings of tight construction (for example, weather

stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in Combustion
Air and Ventilation for Appliances Located in Confined Spaces.

Combustion Air and Ventilation

for Appliances Located in

Confined Spaces

Confined Space is a space whose volume is less than 50 cubic feet per

1,000 Btu per hour of the aggregate input rating of all appliances

installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:

(See Page 10 Figure 1, and Figure 6 below)

1Ъе confined space shall be provided with two permanent openings
communicating directly with an additional foom(s) of sufficient
volume so that the combined volume of all spaces meets the criteria
for an unconfined space. 1Ъе total input of all gas utilization equip­
ment installed in the combined space shall be considered in making

this determination. Each opening shall have a minimum free area of

one square inch per 1,000 BTU per hour of the total input rating of
all gas utilization equipment in the confined space, but not less than

100 square inches. One opening shall commence within 12 inches

of the top and one commencing within 12 inches of the bottom of

the enclosure.

VENT THROUGH

ROOF

Installation Instructions (cont’d)

Figure 8

3. When communicating with the outdoors through horizontal

ducts, each opening shall have a minimum free area of 1 square
inch per 2,000 BTU per hour of total input rating of all equip­
ment in the enclosure. (See Figure 9.)

г

1

^

_,.Â

OPENINGS

VVATER

1

HEATER

!J

Figure 6

VENT TO

; OUTDOORS

Figure 9

b. ALL AIR FROM OUTDOORS: (see Figures 7-9)

The confined space shall be provided with two permanent openings,

one commencing within 12 inches of the top and one commencing

within 12 inches from the bottom of the enclosure. The openings

shall communicate direcdy, or by ducts, with the outdoors or spaces
(crawl or attic) that freely communicate with the outdoors.

4. When ducts are used, they shall be of the same cross-sectional area

as the free area of the openings to which they connect. I’he mini­
mum short side dimension of rectangular air ducts shall not be
less than 3 inches. (See Figure 9.)

5. Louvers and Grilles: In calculating free area, consideration shall be

given to the blocking effect of louvers, grilles or screens protect­
ing openings. Screens used shall not be smaller than

%

inch mesh.

If the free area through a design of louver or grille is known, it
should be used in calculating the size opening required to provide
the free area specified. If the design and free area is not known, it
may be assumed that wood louvers will be 20-25 percent free area
and metal louvers and grilles will have 60-75 percent free area.
Louvers and grilles shall be fixed in the open position or inter­
locked with the equipment so that they are opened automatically
during equipment operation.

6. Special Conditions Created by Mechanical Exhausting or

Fireplaces: Operation of exhaust fans, ventilation systems, clothes
dryers or fireplaces may create conditions requiring special atten­
tion to avoid unsatisfactory operation of installed gas utilization
equipment.

12

Advertising
This manual is related to the following products: