Installation Instructions (cont’d)

ALL MODELS — VENTING THROUGH WALL
OPTIONAL r VENT PIPING

2" DIA.VENT

MAX. LENGTH fFT.)

NUMBER OF 90° DEG.

ELBOWS*

50

1

45

2

40

3

35

4

30

5

25

6

' NOTE: Two 45° elbows are equivalent to one 90° elbow.

One 90° elbow equals 5 feet of equivalent vent length.

ALL MODELS (3 " VENT)

See tables for max> length.

1. Tbe total vertical and horizontal vent run cannot exceed the

maximum

length with the number of 90° elbow as specified

in the following tables. If more elbows are required, the vent­
ing distance must be reduced 5 feet for every 90° elbow:

2. Minimum vent length for all models is 4 feet.

ALL MODELS — VENTING THROUGH WALL

3 " DIA.VENT

NUMBER OF 90° DEG.

MAX. LENGTH fFT.)

ELBOWS*

1 15

1

110

2

105

3

100

4

95

5

90

6

19