Troubleshooting

Troubleshooting

You can refer to the following information to troubleshoot problems. In addition, you may want to refer to the 

DeviceMaster UP Hardware and Configuration Guide

.

Issue

Possible Corrective Action

What are the slot numbers for 

serial and Ethernet input and 

output?

Use the slot number to determine whether the input and output is for a serial port 

or a TCP/IP port. Serial input is received in Slot 1, serial output is sent through Slot 

11, TCP/IP input is received in Slot 21 and TCP/IP output is sent through Slot 31. 

This will eventually allow us to handle I/O for Ports 2‐4 in Slot 2, 3 and 4 or there 

corresponding ports in the 10s, 20s and 30s range.

What if the system fault light is 

on? 

Look at the hardware diagnostics for the CPU that the DeviceMaster UP should 

be connected to.

Examine any faults and take corrective action.

Ensure that your device is assigned the correct PROFINET IO Device Name 

using HW Config.

Ensure that all the components are properly plugged in and powered on.

What if I never see data 

appearing in PLC Input 

memory? 

Verify that there are no faults having to do with the DeviceMaster UP.

Verify that the PLC is in RUN mode.

Verify that you are looking at the correct Input address as assigned in the HW

Config

 tool.

What if after writing data to 

output memory it doesn't 

appear?

Verify that you are writing to the Output Memory address you configured in 

HW Config

.

Verify that you are setting the Sequence Number and Length fields correctly in 

the Output Memory.
The DeviceMaster UP Output Memory begins with two WORD values; a 16‐bit 

Sequence Number and 16‐bit Length field at the beginning of every “packet” of 

serial or Ethernet data. The sequence number allows you to control when a new 

packet is sent by incrementing the outgoing sequence number. See Step 

4

 in 

Configuring Read/Write Devices

 on Page 6.

Verify that no system faults are occurring on PLC or DeviceMaster UP.

What if I miss some data from 

the PLC – i.e. it never seems to 

arrive?

PNIO is a cyclic I/O protocol. That is, data is exchanged between the PLC and the 

DeviceMaster UP every N milliseconds. The frequency of the update is controlled (as 

with all PNIO devices) in the IO Cycle tab of the Properties window for the 

DeviceMaster UP. This is accessed by double‐clicking on the device in the HW
Config

 application from within Step7. Update rates from 8ms to 512ms are available 

in power of two increments.

If you are not getting the information from the serial device soon enough, you 

may have the update rate configured to be too slow in the HW Config.

Is the connection dropping? Verify that you are not seeing system faults in the 

history. 

I can't find the DeviceMaster UP 

device in HW Config!

It should be under PROFINET IO – Additional Field Devices – Gateway. If it is not 

there, try reinstalling the GSDML file. 