DeviceMaster UP PROFINET IO Installation Quick Start

2000484 Rev. E ­ 7

Configuring Read/Write Devices

(see table below) in the output buffer. The length field is two bytes, and starts at the 2nd byte.

Triggering the send. The data will not be sent through the serial port until the DeviceMaster UP sees that 

the sequence number in the Output data is incremented. The DeviceMaster UP is informed of the new 

sequence number during the next I/O cycle. So, with a cycle time of 32ms (specified in Step7 the 

DeviceMaster UP will begin sending the data within 32ms. The data will be only sent once, and no further 

data will be sent until the sequence number is again updated. This prevents the same data from being sent 

over and over out the serial port.

Verifying that the data has been sent. If you wish to confirm that the last data written to the output data 

area has been sent out the serial port, check the input memory for the same output module. This 16‐bit 

integer is the last data packet that was sent out the serial port. So, to confirm that the current packet has 

been sent, compare the sequence number (a WORD) in the output data with the input data for that module. 

In the screen shot (above), we would compare PIW 600 with QW 608. If they are the same, the data has been 

sent.

Writing Out the Socket Port

Use the correct slot. To write data out the socket port, place an Output module in Slot 31. Slot 31 is the 

only slot that can be used to write Output data to the socket. The input and output modules for socket 1 are 

shown below with 220 byte buffers.

The remaining steps are exactly the same as those for writing out a serial port. Only the slot changes.

Field Name

Offset in BYTES

Data Type

Data Value(s)

Sequence number

0

WORD

0‐65536 (0xFFFF Hex)

Data length (in BYTES)

2

WORD

0‐220

Data 

4

Array of BYTEs

User controlled