4 ­ 2000484 Rev. E

DeviceMaster UP PROFINET IO Installation Quick Start

Configuring Read­Only Ethernet TCP/IP Devices

The format of data sent to a PNIO controller:

More than 220 bytes of data can not be received by the PNIO controller.

Configuring Read­Only Ethernet TCP/IP Devices

Use the following procedure to configure read‐only socket devices.
Note: Make sure that you have performed

Steps 1 through

5 in the

Installation Overview

on Page 1.

1. Access the Server Configuration web page using one of the following methods:

Entering the IP address in your web browser

Right‐click the DeviceMaster UP in PortVision DX and click Web Manager

2. Click on Ethernet Device Configuration to open the Ethernet Device Configuration page.
3. Click the Socket # that you want to configure, which opens the Edit Socket Port Configuration page.

Note: Refer to your Ethernet device's User Manual for the following settings.

4. Under Device TCP Connection Configuration

select Enable.

If your Ethernet TCP/IP device requires 

another device to connect to it, configure 

the socket port on the DeviceMaster UP 

to Connect mode:

Leave Listen unselected.

Set Connect To Mode to Connect-
Always

.

Set the Connect Port to the socket 

port number of your Ethernet 

device.

Set the Connect IP Address to the IP address of your Ethernet device.

Set Disconnect Mode to Never.

If your Ethernet TCP/IP device is 

configured to connect to another device, 

configure the socket port on the 

DeviceMaster UP to Listen mode: 

Select Listen.

Use the default Listen Port on the 

DeviceMaster UP of 8xxx or 

designate your own.

Set Connect To Mode to Never.

Set Disconnect Mode to Never.

Configure your Ethernet device to connect to the DeviceMaster UP at the DeviceMaster UP IP address and 
Listen Port

.

Name

Data Type

Data Value(s)

Receive (DeviceMaster to PLC message data.

Structure of:

Produced data sequence

Data length (in bytes)

Data array

WORD

WORD

Array of BYTE

0‐65535 (

FFFF Hex

)

0‐220

0‐255