mAI085-MB Actuator Interface Technical Manual /7

Distributive Intelligence

CMC INDUSTRIAL ELECTRONICS LTD

3.2 Optional Extended Data Network

Host Computer

or PLC

SV

OL

IDL

POS

FLT

MOV

OPN

CLS

EMP

PV

OPEN

CLOSE

CLEAR

SET

SCAN

CMC INDUSTRIAL ELECTRONICS

ACTUATOR INTERFACE

24VDC

1.25A

Controller

1 - 30

4 conductor

communications

cable RS-485

Modbus RTU

RS-232

Controller

61 - 90

Controller

31-60

Controller

91 - 100

RS-485

repeater

Phoenix

Contact

2744429

RS-485

repeater

Phoenix

Contact

2744429

RS-485

repeater

Phoenix

Contact

2744429

Figure 4 - Extended Data Network

The interface can accommodate up to 100 actuator controllers if RS485 repeaters are used. A
typical repeater is the Phoenix Contact Part No. 2744429 optical isolated repeater. Up to 30
controllers can be on a single network segment (31 for the end of line). Using repeaters, a
linear network as shown above, or various forms of star or tee networks can be deployed as
required. The start of a branch on either a star or tee network must always begin with a
repeater.

A network expansion RS232 port is also provided. This port can connect directly to repeaters or
fiber-optic cable drivers. Controllers can be connected to both the standard RS485 port and the
expansion RS232 port. The port is designated J1 and is a female DB9 connector. It is wired
DTE.