mAI085-MB Actuator Interface Technical Manual /4

Distributive Intelligence

CMC INDUSTRIAL ELECTRONICS LTD

ID

Label

Description of Operation

7

Clear key and
lamp

Clears all actuator setpoints. First press illuminates the lamp, the second
press clears the setpoints and turns off the lamp. The lamp will turn off
automatically after 10 seconds if the key is not pressed the second time
and the setpoints will not be cleared.

If the CLEAR lamp is illuminated continuously and the operator keyboard
does not function, the keyboard has been locked by the Modbus
interface. Pressing and holding the CLEAR key for 10 seconds will
unlock the keyboard. The CLEAR lamp will extinguish when the
keyboard is unlocked. The setpoints will not be cleared during this
operation.

8

Open / Close keys
and indicators

Opens or closes the actuators to their pre-set values. The indicators
display which mode is active.

9

Process Value

Displaying the actuator position

10 Status Indicators

MOV - actuator is currently moving to setpoint

OPN – if configured, indicates the actuator is fully open

CLS - if configured, indicates the actuator is fully closed

EMP - if configured, indicates the bin served by the actuator is empty

11 Fault Indicators

OL – if configured, the actuator has faulted due to excess running current

IDL - if configured, the actuator has faulted due to excess idle current

POS – the actuator failed to reach the selected position

FLT – the actuator controller is not communicating or has a hardware
fault

12 Scan key

Press once to scan through all controllers at 1 second intervals. Press
the SCAN key again to cancel scanning. Pressing the up or down
actuator selection keys also cancels scanning.

Table 1 - Description of Keys and Indicators