mAI085-MB Actuator Interface Technical Manual /16

Distributive Intelligence

CMC INDUSTRIAL ELECTRONICS LTD

5.3.1 Main Menu

The Main Menu allows the selection of several sub-menus and selection of the global
parameter functions. All Main Menu items require YES/no responses.

Display Function

Response

LoC

Go to the local interface parameters menu.

YES/no

CtL

Go to the configure actuator controllers menu.

YES/no

bUs

Go to the configure ModBus RS232 interface menu.

YES/no

FAC

Go to the reset factory values Menu

YES/no

SAv

Save the current configuration to non-volatile storage. A YES response
will display SUrE in the lower display. A second YES response will save
all parameters to non-volatile storage. The lower display will indicate
the progress of the operation. When the operation is completed
successfully, the lower display will show donE. Should the operation
not complete successfully the lower display will show FAiL. If the
operation fails, repeat the save. Should repeated attempts to save the
parameters fail, the non-volatile storage is damaged and the unit should
be replaced.

YES/no

rCL

Recall the last saved configuration from non-volatile storage. This
operation is done automatically during normal startup of the interface.
The last saved configuration can be recalled by answering YES to this
item. A YES response to the SUrE display will restore all interface
parameters from non-volatile storage.

***************************** WARNING ********************************

This function will overwrite the current Interface parameter table
with the last saved table. All current adjustments to the table will
be lost.

***************************************************************************.

YES/no

Fnd

Find all active controllers on the network. A YES response displays
SUrE in the lower display. The second YES response starts the
operation. The upper display indicates the actuator controller address
and the lower display the result of the query. All 100 addresses are
queried (1-100). Each controller, if found, will display YES on the lower
display. Unused addresses will show no. Once complete, the lower
display shows DonE. The Active flag for each controller is set or
cleared during this operation. Each address is tried 5 times.

YES/no

GEt

Gets the operational parameters from all actuator controllers marked
active. A YES response displays SUrE in the lower display. The

YES/no