External connections – CMC electronic MAI085MB User Manual

Page 9

Advertising
background image

mAI085-MB Actuator Interface Technical Manual /5

Distributive Intelligence

CMC INDUSTRIAL ELECTRONICS LTD

3. External Connections

1

2

3

4

9

10

V-

V+

G

V-

V+

SH

D_L

D_H

6

5

7

8

11

13

12

Figure 2 - Terminal Blocks and Connectors

ID

Label

Description

1

Output 1

Contact will close if in open mode or to start the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC

2

Output 2

Contact will close if in close mode or to stop the conveying system.
Maximum load 1A @24VDC, 0.5A@120VAC

3

Output 3

Contact will close if all setpoints are at zero.
Maximum load 1A @24VDC, 0.5A@120VAC

4

Output 4

Contact will close if the interface has an internal fault.
Maximum load 1A @24VDC, 0.5A@120VAC

5

Inputs 1

Energizing will select open mode.

6

Inputs 2

Energizing will select close mode.

7

Inputs 3

Energizing will clear all setpoints to zero.

8

Inputs 4

Energizing will force all actuators closed without affecting open/close
mode selection. Blending timers are ignored during a force close.