CMC electronic MAI085MB User Manual

Page 34

Advertising
background image

mAI085-MB Actuator Interface Technical Manual /30

Distributive Intelligence

CMC INDUSTRIAL ELECTRONICS LTD

Register

Function

40002

Controller 1 Process value

40003

Controller 1 Status

40004

Controller 2 Process value

40005

Controller 2 Status

40006

Controller 3 Process value

40007

Controller 3 Status

~

~

40200

Controller 100 Process value

40201

Controller 100 Status

The controller process value is a 12 bit unsigned integer. The process value will occupy bits 0 -
11 of the process value word. The factory set range of the process value will be from 0 - 100,
signifying 0 - 100%. The controller status word definition is as follows:

Bit

Function

0

Input 1 (Force Close) , 1 = input lamp off

1

Input 2 (Closed Limit) , 1 = input lamp off

2

Input 3 (Open Limit) , 1 = input lamp off

3

Input 4 (not assigned), 1 = input lamp off

4

Seek in progress, 1 = seeking

5

Motor running, 1 = running

6

Motor direction, 1 = close

7

not used, always 0

8

Position fault, 1 = did not reach position

9

Over fault, always 0, not implement in mGP145

10

Idle Load fault, always 0 not implement in mGP145

11

Parameter fault, 1 = parameters corrupted

12

Firmware fault, 1 = controller failed

13

Bad command, 1 = last command invalid

14

Calibration mode, 1 = in calibration mode

15

Communications fault, 1 = no communications

Advertising