Water quality, Description, Instructions for connections – LAARS IGE-199C - Installation Manual User Manual

Page 11: Warning, Notice

Advertising
background image

SECTION V: WATER CONNECTIONS

WARNING

Failure to install and maintain a new, listed pressure relief valve will release the manufacturer from any

claim, which might result from excessive temperature and pressures.
Keep clear of the pressure relief valve discharge line outlet. The discharge may be hot enough to cause

scald injury. The water is under pressure and may splash.

WARNING

DO NOT reverse the inlet and outlet (cold and hot water) connections on the water heater. This may

cause a hazardous operating condition or the water heater may be inoperable

WATER QUALITY

The EVERHOT® water heater must have the water quality within the following limits for long life and

reliable operation (see Table 2). The water supply should be tested to make sure the quality is within the

specified limits. If there is a problem with the water quality, contact your local water conditioning company

for equipment to condition the water supply to this appliance.

NOTICE

Operating this water heater with water conditions outside the specified limits will void the warranty.

Table 2

Description

pH

TDS

(Total

Dissolved

Solids)

Total

Hardness Aluminum Chlorides Copper Iron Manganese Zinc

Levels

6.5 to

8.5

Up to 500

ppm

Up to

200 ppm

or 11.7

grains of

hardness

Up to 0.2

ppm

Up to

250 ppm

Up to

1.0 ppm

Up to

0.3

ppm

Up to 0.05

ppm

Up to

5 ppm

Lime Condition Warning Signal:

If the EVERHOT water heater is operated under hard water conditions without a water conditioner, the

error code “LC” may flash on the remote temperature display. This code means the heat exchanger coil

is beginning to accumulate scale deposits and MUST be flushed (see Section IX, “Flushing Procedure for

Lime Scale Removal…”). Contact your installer for a qualified service technician to flush the heat

exchanger. A water conditioner may be needed to prevent this condition from reoccurring.

NOTICE

Failure to flush the appliance when “LC” is flashing will cause damage to the heat exchanger. Damage

caused by lime or scale build up is not covered by the water heater warranty.

INSTRUCTIONS FOR CONNECTIONS

1. BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY

VALVE. After shutting off the main water supply, open a faucet to relieve the water line pressure

to prevent any water from leaking out of the pipes while making the water connections to the

water heater. The COLD water inlet and HOT water outlet are identified on the bottom casing of

the water heater. Make the proper plumbing connections between the water heater and the

plumbing system to the house. All soldering materials and piping must be compatible with

potable water. Unions should be installed on both the hot and cold water lines for future servicing

and disconnection of the water heater. Install a shut-off valve in the cold water supply line.

11

Advertising
This manual is related to the following products: