Gas meter size –naturalgas only, Gas pressure regulation, Initial operation and testing (installer only) – LAARS IGE-199C - Installation Manual User Manual

Page 19: Warning

Advertising
background image

Check the type of gas and the gas inlet pressure before connecting the EVERHOT water heater to the

gas supply. If the gas supply type does not match the type shown on the water heater rating plate, then

DO NOT connect the water heater. Contact your supplier for the correct water heater.

GAS METER SIZE –NATURAL GAS ONLY

Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as

well as the requirements of all other gas fired equipment supplied by the meter. If the gas meter is too

small, ask the gas company to install a larger meter having adequate capacity.

GAS PRESSURE REGULATION

Minimum and maximum gas supply pressures are listed below: The minimum gas pressure specified

below is required for the full input rating specified on the water heater rating plate.

Natural Gas

: Minimum: 6.0” w.c.

L.P. Gas:

Minimum: 10.0” w.c.

Maximum: 10.5” w.c.

Maximum: 13.5” w.c.

BEFORE PLACING THE WATER HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. USE SOAP

AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING

GAS LEAKS.

WARNING

DO NOT use matches, candles, flame or other sources of ignition for this purpose.

Capacity Table for Natural Gas in Cubic Feet/Hour

(Table assumes 0.3 inch pressure drop, specific gravity of 0.60 for gas pressures of 0.5 psi or less)

Length of Pipe in Feet (Meters)

10 20 30 40 50 60 70 80 90 100

125

150

175

200

Pipe

Size in

Inches (3) (6) (9) (12) (15) (18) (21) (24) (27) (30) (38) (45) (53) (61)

3⁄4”

278 190 152 130 115 105 96 90 84 79 72 64 59 55

1”

520 350 285 245 215 195 180 170 160 150 130 120 110 100

1

1⁄4” 1050 730 590 500 440 400 370 350 320 305 275 250 225 210

1

1⁄2” 1600 1100 890 760 670 610 560 530 490 460 410 380 350 320

Note: After determining the length of pipe required, select the pipe size that will supply the cubic feet per

hour of gas required for the input rating of the gas appliances on the line.

The formula for figuring the cubic feet per hour required is:

CFH = Gas Input of Appliance on the Line (Btu/hr)

Heating Value of Gas (Btu/Cu. Ft.)

The heating value may be obtained from the local natural gas utility

Capacity Table for LP Gas in MBH of undiluted liquefied petroleum gases

(Table assumes 11 inches of water column pressure at the inlet, 0.5” press. drop)

Length of Pipe in Feet (Meters)

10 20 30 40 50 60

70

80

90

100

125

150

Pipe

Size in

Inches

(3) (6) (9) (12)

(15)

(18)

(21)

(24)

(27)

(30)

(38)

(45)

1⁄2” 275 189 152 129

3⁄4” 567 393 315 267 237 217 196 185 173 162 146

1” 1071 732 590 504 448 409 378 346 322 307 275 252

1

1/4” 2205 1496 1212 1039 913 834 771 724 677 630 567 511

INITIAL OPERATION AND TESTING (INSTALLER ONLY)

1. Open the gas and water supply valves to the water heater.

2. Check for water and gas leaks. Use soap solution to check for gas leaks.

3. To check inlet supply pressure, remove the 1/8” NPT plug on the gas inlet supply fitting just below

the bottom casing and install a barb fitting for attaching a hose to a manometer. For checking the

gas manifold pressure, the plug is located just below the gas manifold connection inside the

control panel.

19