3 feet (0.9m) horizontally from the combustion

air terminal, and locate the vent terminal at least

1 foot (0.3m) above the combustion air terminal.

WARNING

The outdoor vent terminal gets hot. Unit must be

installed in such a way as to reduce the risk of

burns from contact with the vent terminal.

AVERTISSEMENT

La sortie d’évent à l’extérieur devient très chaude.

Elle doit être installée de façon à réduire le risque

de brûlures au contact de l’extrémité de l’évent.

Important Note: Massachusetts Code Requirement.

From Massachusetts Rules and Regulations 248

CMR 5.08:

(a) For all side wall horizontally vented gas

fueled equipment installed in every dwelling,

building or structure used in whole or in

part for residential purposes, including those

owned or operated by the Commonwealth and

where the side wall exhaust vent termination

is less than seven (7) feet above finished grade

in the area of the venting, including but not

limited to decks and porches, the following

requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE

DETECTORS.

At the time of installation of the side wall

horizontal vented gas fueled equipment, the

installing plumber or gasfitter shall observe that

a hard-wired carbon monoxide detector with

an alarm and battery back-up is installed on

the floor level where the gas equipment is to be

installed. In addition, the installing plumber or

gasfitter shall observe that a battery operated or

hard-wired carbon monoxide detector with an

alarm is installed on each additional level of the

dwelling, building or structure served by the side

wall horizontal vented gas fueled equipment.

It shall be the responsibility of the property

owner to secure the services of qualified licensed

professionals for the installation of hard-wired

carbon monoxide detectors.

a. In the event that the side wall

horizontally vented gas fueled equipment

is installed in a crawl space or an attic, the

hard-wired carbon monoxide detector with

alarm and battery back-up may be installed

on the next adjacent floor level.

b. In the event that the requirements of

this subdivision cannot be met at the time of

completion of installation, the owner shall

have a period of thirty (30) days to comply

with the above requirements; provided,

however, that during said thirty (30) day

period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE

DETECTORS.

Each carbon monoxide detector as required

in accordance with the above provisions shall

comply with NFPA 720 and be ANSI/UL 2034

listed and IAS certified.

3. SIGNAGE.

A metal or plastic identification plate shall be

permanently mounted to the exterior of the

building at a minimum height of eight (8) feet

above grade directly in line with the exhaust vent

terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall

read, in print size no less than one-half (½) inch

in size, “GAS VENT DIRECTLY BELOW.

KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION.

The state or local gas inspector of the side

wall horizontally vented gas fueled equipment

shall not approve the installation unless, upon

inspection, the inspector observes carbon

monoxide detectors and signage installed in

accordance with the provisions of 248 CMR

5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is

exempt from 248 CMR 5.08(2)(a) 1 through 4:

1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the

most current edition of NFPA 54 as adopted by

the Board; and

2. Product Approved side wall horizontal vented gas

fueled equipment installed in a room or structure

separate from the dwelling, building or structure

used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS –

GAS EQUIPMENT VENTING SYSTEM

PROVIDED. When the manufacturer of

Product Approved side wall horizontally

vented gas equipment provides a venting

system design or venting system components

with the equipment, the instructions provided

by the manufacturer for installation of the

equipment and the venting system shall

include:

1. Detailed instructions for the installation of the

venting system design or the venting system

components; and

2. A complete parts list for the venting system