LAARS Pennant PNCV - Install and Operating Manual User Manual

Page 35

Advertising
background image

Low Temperature Pennant

Page 35

SECTION 8.

Trouble Shooting

8.1 Resolving Lockouts

There are many causes of lockouts. The three

most common causes are: (1) inadequate gas supply,

(2) poor combustion, (3) ignitor failure.

1. Inadequate gas supply: Before proceeding, ensure

that the gas supply has not been shutoff or the LP

tank (LP boilers) is not empty. Then, restart the

boiler and observe the operational cycle. After

a 15-second fan pre-purge, the ignitor will heat

up for 40 seconds, and then the unit will light.

If it does not, check the gas supply pressure to

the appliance, after resetting the appliance and

attempting another start-up. The gas pressure to

the appliance must be above 5 in. w.c. (1.2 kPa)

throughout the entire start-up cycle. If it is not,

correct the supply problem (check gas valves or

supply piping). If the supply pressure is adequate,

consult the factory for assistance.

2. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from an improper gas/air ratio

(high or low O

2

or CO

2

). Pennant appliances

operate best with 45% excess air (8% CO

2

on

natural gas, 9.2% CO

2

on LP). Check the CO

2

of

the appliance and adjust if necessary.

3. Ignitor failure: If the boiler goes through a

normal start cycle but combustion does not

occur, ignitor failure should be suspected. Check

the ignitor by unplugging the ignitor plug and

measuring the ignitor resistance. It should be

50-80 ohms. If the resistance is not 50-80 ohms,

replace the ignitor. If the resistance is correct,

reset the boiler and check for 120 VAC at the

ignitor plug during the start cycle. If there is no

voltage, replace the faulty ignitor wire harness or

the ignition control.

8.2 Delayed Ignition — Possible Causes

A defective burner can cause a delayed ignition.

If the gas supply pressure is proper and the gas

valves are functioning properly, then burners should

be inspected. There should be no distortion or

perforations in the burners outside of the active burner

port area. Replace if indicated.

8.3 Short Cycling — Boiler

Boiler short cycling is caused when the

load on the boiler system swings rapidly causing

frequent cycling between call for heat and satisfied

conditions. If short cycling is a problem, it may be

due to an oversized boiler, improper control strategy,

incorrect set points or a load distribution problem.

The boiler controls must be set such that the heating

loop temperature setpoint does not interfere with

1. Disconnect the electrical supply to the unit.

2. Turn off the gas supply by closing the manual gas

valve on the heater.

3. Disconnect and remove the wires, conduit and

sensors from all components that are attached to

the inlet/outlet header.

4. Isolate the heat exchanger from the water supply.

5. Disconnect the header flanges from the inlet and

outlet.

6. Allow the heat exchanger to drain. Remove the

front cover(s) by removing the rubber access

strip(s) and the retaining screws. Remove the

venting and remove the top, by removing the

screws that attach the top to the side panels.

Remove the side panels. Remove the front lower

panels sealing the combustion area. To remove

the gas train, disconnect the unions located

below the intermediate pan and the field installed

union located outside the cabinet, and pull up,

bringing the union end connectors through the

grommets in the intermediate pan. To remove the

intermediate pan, remove the slide out control

assembly and blower(s) to reveal the screws.

Remove the screws holding the intermediate pan,

and lift up to remove it. The heat exchanger has

integral metal sections attached, which connect

to the frame of the boiler. Locate and remove

the screws along the front, rear and bottom of

the integral metal sections, and remove the heat

exchanger and metal sections by lifting up. On

the larger appliances, a center heat exchanger

support must be unbolted before it can be

removed..

7. Remove the heat exchanger from the unit.

NOTE: Heat exchangers are heavy and may

require two people to remove to avoid personal

injury.

8. Clean the heat exchanger: A light accumulation

of soot or corrosion on the outside of the heat

exchanger can be easily removed. Use a wire

brush to remove loose soot and scale from the

heat exchanger.

9. NOTE: While the heat exchanger is out of the

unit, inspect the firewall refractory insulation.

Replace if necessary.

10. Inspect the inside of the copper tubes for scale

buildup. Scale can build up on the inner surface

of the heat exchanger tubes, which can restrict

water flow. If the tubes show signs of scaling,

clean the internal surface.

11. Reassemble in the reverse order, and check

appliance operation after start-up.

NOTE: The warranty does not cover damage

caused by lack of required maintenance, lack of

water flow, or improper operating practices.

Advertising
This manual is related to the following products: