Low Temperature Pennant

Page 33

7.2.2 Filter

The filter used in the Pennant is washable. Since

the filter is washable, it will only need replacement

occasionally. If filter replacement is needed, it should

only be replaced with a factory part. Inspect the air

filter monthly, or more often in dirty environments. If

there is debris on the air filter, remove it from the filter

box, and wash it with mild soap and water. Ensure that

the filter is completely dry before reinstalling.

7.2.3 Gas Valves

The gas valves are designed to operate with

supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).

To remove a valve, shut off 120-volt power

and the manual gas shutoff valve. Remove the top

front panel from the unit. Disconnect the wires to the

valve. Disengage the flanged fitting before and after

the valve, and remove the valve. Re-install in reverse

order. Ensure o-rings are properly installed for both

inlet and outlet. Turn on manual gas shutoff valve and

120 volt power and check appliance operation and

tightness of gas valve connections.

7.2.4 Manual Reset High Limit Control

The high limit switch is manual reset switch with

an adjustable set point, up to 240°F (116°C) on boiler

models and 200°F (93°C) on water heater models

and boilers ordered with low temperature controls. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull

the switch off the control panel. Remove the capillary

and bulb from the thermal well located in the header.

Replace in reverse order.

7.2.5 Automatic Reset High Limit Control

An automatic reset high limit is used in addition

to the manual reset high limit. The high limit switch

has an adjustable set point, up to 240°F (116°C) on

boiler models and 200°F (93°C) water heater models

and boilers ordered with low temperature controls. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull

the switch off the control panel. Remove the capillary

and bulb from the thermal well located in the header.

Replace in reverse order.

7.2.6 Temperature Control

The temperature control is an on/off control that

also manages the mixing system.

To replace the control, disable the 120v supply

power to the appliance. Unplug all of the electrical

connectors, remove the retainer clip and the control.

Replace the control in the reverse order.

7.2.7 Ignition Control

The ignition controls ensure the proved interrupt-

ed-type ignition system. They control the hot surface

ignitors and prove that the flame signal is appropri-

Figure 18. Typical Control Panel.