above grade such that blockage of the terminal from

accumulated debris or precipitation is prevented.

The dimensions and requirements that are shown

in

Table 1

should be met when choosing the locations

for the appliance.

1.6 Locating Pump-Mounted Water Heater

with Respect to Storage Tank(s)

For best results, the Pennant water heater should

be located within 15 feet (4.6m) of the storage tank(s).

The pump is sized for 30 feet (9.1m) of piping.

If the appliance must be installed with longer

piping runs, then larger diameter pipe or tubing may be

acceptable. Consult the factory for assistance.

Size

Vent Collar

Size

Horizontal

Vent Pipe

Diameter

Intake

Air Collar

& Pipe

Diameter

Max. Pipe

Length

Max. No.

of Elbows

Side Vent

Terminal

Part Number

Side Wall

Combustion

Air Terminal

Part Number

in

cm

in

cm

in

cm

ft

m

500

8

20

6

15

6

15

50

15

3

CA001401

20260701

750

10

25

8

20

6

15

50

15

3

CA001401

20260701

1000

10

25

8

20

8

20

50

15

3

CA001402

20260703

1250

12

30

8

20

8

20

50

15

3

CA001403

20260703

1500

12

30

8

20

8

20

50

15

3

CA001403

20260703

1750

14

36

8

20

8

20

50

15

3

CA001403

20260703

2000

14

36

12

30

12

30

50

15

3

CA001404

20260706

Table 2. Horizontal Vent / Combustion Air Parameters.

Appliance

Surface

Required

Clearance From

Combustible Material

Recommended

Service Access

Clearance

inches

cm

inches

cm

Left Side

1

2.5

24

61

Right Side

1

2.5

24

61

Top

1

2.5

12

30

Back

1

2.5

12**

30**

Front

1

2.5

36

91

Vertical

(Category 1)

Vent

6*

15.2*

Horizontal

(Category 3)

Vent

per UL 1738 venting

system supplier's

instructions

*1" (2.5 cm) when b-vent is used.

**When vent and/or combustion air connects to the back,

recommended clearance is 36" (91cm).

Table 1. Clearances.

1.7 Locating Pump-Mounted Boiler with

Respect to Return/Supply Header

For the best results, Pennant should be located

within 15 feet (4.6m) of the supply and return headers.

The pump is sized for 30 feet (9.1m) of piping.

If the appliance must be installed with longer

piping runs, then larger diameter tubing may be

acceptable. Consult the factory for assistance.

1.8 Locating Appliance for Correct

Horizontal Vent/Ducted Air Distance

From Outside Wall

The forced draft combustion air blower(s) in the

appliance has/have sufficient power to pull air and vent

properly when the guidelines for horizontal air and

vent are followed (see

Table 2

).

NOTE: On some models, the vent collar size is

larger than the size of the vent pipe that can be

used. Vent collar size and horizontal pipe diameters

can be found in Table 1. The larger vent collar

size is to accommodate Category I (vertical) vent

systems.
NOTE: When located on the same wall, the

Pennant combustion air intake terminal must

be installed a minimum of 12" (30cm) below the

exhaust vent terminal and separated by a minimum

of 36 inches (91cm) horizontally.

The air intake terminal must be installed high

enough to avoid blockage from snow, leaves and other

debris.