LAARS Pennant PNCV - Install and Operating Manual User Manual

Page 34

Advertising
background image

LAARS Heating Systems

Page 34

ate for powering the gas valves. It also controls the

blower’s pre-purge and post-purge. Pennant models

500 through 1000 have one ignition control. Models

1250 through 2000 have two ignition controls.

To replace a control, shut off the 120-volt power

to the appliance. Remove the cover from the control

panel. Remove the electrical connectors from the

ignition control. Take out the controller’s mounting

screws, and pull the controller out. Replace in reverse

order.

7.2.8 Ignitor

The ignitors used are 120v “Hot Surface” type.

They are energized whenever there is a call for heat

and switched off when ignition is established and the

flame has been sensed. Pennant models 500 through

1000 have one ignitor. Models 1250 through 2000

have two ignitors. To replace the ignitor, shut off the

120-volt power to the appliance, remove the ignitor

access panel, disconnect the Molex connector, remove

the two mounting screws on the ignitor flange, and pull

the ignitor out. Install in reverse order, always using a

new ignitor gasket with the replacement ignitor.

Caution

Ignitor gets hot. To avoid injury, handle the ignitor

with caution.

Attention

Le dispositif d’allumage devient très chaud.

Manipulez le dispositif d’allumage avec précaution.

7.2.9 Transformer

The Pennant’s transformer is not capable of

supplying control voltage for external devices such

as zone valves, which must have their own separate

power supply.

Some Pennant units have more than one

transformer, and all transformers are not the same

size, so ensure that replacement transformers are the

appropriate ones.

Should a transformer need replacing, shut off the

120-volt power. Unplug the transformer wires, remove

the mounting screws and remove the transformer.

Replace transformer in the reverse order.

7.2.10 Blowers

The combustion air blowers bring the combustion

air for the Pennant from the upper chamber to the

lower chamber. Mixing of the gas and air occurs in the

burners. Models 500, to 1000 each have one blower,

and models 1250 to 2000 each have two blowers.

If a blower change is required, turn off the 120-

volt power and gas supply to the unit. Remove the

front panel. Disconnect the blower’s wire harness.

Remove the screws at the blower flange, and pull the

blower out. Replace blower in reverse order, ensuring

that all joints are made correctly. After replacement,

ensure that the unit operates properly, by following the

set-up procedure in this manual.

7.2.11 Flow Switch

The Pennant uses a paddle-type flow switch to

ensure that the unit has water flow before ignition is

allowed. To replace the flow switch, turn off the 120-

volt power to the appliance. Isolate the boiler or water

heater from the system by closing the isolation valves.

Caution

Water may be hot enough to scald. Allow water to

cool before proceeding.

Attention

L’eau peut être chaude au point de vous brûler.

Laissez refroidir l’eau avant d’intervenir.

Release pressure in the system by actuating

the pressure relief valves or field supplied boiler

drain valve. Remove cover from the flow switch

and disconnect the wires. Unthread the flow switch

from piping. Ensure the new flow switch paddles are

trimmed to the same size as the original paddles, and

reinstall in the reverse order. For boiler and other static

pressure systems, restore the system pressure to the

original setting (or 10 psi minimum).

7.2.12 Heat Exchanger Coil

WARNING

Black carbon soot buildup on a dirty heat exchanger

can be ignited by a random spark or flame thereby

creating a risk of fire or explosion. To prevent this

from happening, dampen the soot deposits with a

wet brush or fine water spray before servicing the

heat exchanger.

AVERTISSEMENT

L’accumulation de suie sur un échangeur thermique

sale peut s’enflammer au contact d’une étincelle ou

d’une flamme et présenter un risque d’incendie ou

d’explosion. Afin d’empêcher que cela se produise,

humidifier les dépôts de suie à l’aide d’une brosse

mouillée ou par une pulvérisation fine d’eau avant

d’effectuer l’entretien de l’échangeur thermique.

The Pennant has a premixed burner system.

These systems provide the burners with sufficient air

for complete combustion, and black carbon sooting is

seldom experienced. If sooting is suspected, view ports

for inspection of the heat exchanger are provided on

the side of the boiler. In the unlikely event that there is

a buildup of black carbon soot or other debris on the

heat exchanger, clean per the following:

Advertising
This manual is related to the following products: