LAARS Pennant PNCV - Install and Operating Manual User Manual

Page 21

Advertising
background image

Low Temperature Pennant

Page 21

Single

Two Circuit

Size

Circuit

Heater Pump

500

20

15 15

750

20

15 15

1000

(TACO) 20 / (B&G) 30

20

15

1250

30

25 15

1500

30

25 15

1750

25 20

2000

25 20

Table 10. Electrical Data (Amps).

Figure 10. Removing Jumpers.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring terminal strip, which is located to the left of the

blower.

NOTE: All internal electrical components have been

pre-wired. No attempt should be made to connect elec-

trical wires to any other location except the wiring box.

5.1 Main Power

5.1.1 Sizes 500-1500

Pennant sizes 500-1500 use a single 120-volt

fused supply. The installer can change the single

service heaters to use a separate circuit for the pump, if

desired. Instructions to make this change are found in

Section 5.1.3

.

Pennant 500-1500 main power (L1, N1 &

Ground) shall be connected to the three wires (10

AWG) supplied. Over-current protection ratings can be

found in

Table 10

.

5.1.2 Sizes 1750-2000

Pennant sizes 1750-2000 require two 120-volt

fused supplies.

Heater circuit can be identified with 10AWG

wires to include black, white and green (all solid

colors). Pump circuit can be identified with three

12AWG wires to include a black wire with a white

tracer (stripe), a white and green wire.

5.1.3 Separate Pump Circuit

Conversion to separate pump circuit will neces-

sitate removing the three jumpers within the internal

wiring of the 120-volt portion of the heater (see

Figure

10

). Only do this with the power disconnected to the

unit!

To rewire the pump circuit, bring in another

120-volt fused supply (L2, N2 & Ground). Connect

incoming power (L2) to the main power switch using

spade (fork) terminal. From the other side of the main

power switch connect to the main terminal block using

a ¼" female insulated quick connect. This will be

the same position where the jumper had terminated

(see

Figure 10

). Connect N2 and Ground to the main

terminal block using ¼" female insulated quick connect

(refer to

Figure 10

).

5.1.4 All Sizes

Ladder diagrams are shown in

Figures 12 and 13

.

Wiring diagrams are shown in

Figures 14 through 16

.

Field wiring is shown in

Figure 11

.

5.2 Field Wiring

Temperature Sensor: The Low Temperature

Pennant is controlled by a sensor that requires place-

ment in the system loop or storage tank. A sensor well

is shipped with the unit, as well. This sensor placement

allows the Pennant to be called for heat, based on the

system temperature. The sensor is wired to terminals

on the Pennant temperature control at the factory.

External Alarm: The field terminal strip has

terminals for a dry contact that is closed when the

ignition control locks out. These terminals are labeled

“ALRM” and “ALRM”.

Additional Call For Heat: Terminals labeled

“COMD” and “HTD” can be used to call the Pennant

for heat. These terminals are shipped with a jumper

between them. Remove the jumper to use these

terminals. The Pennant is controlled by the temperature

sensor, and the temperature must be calling for heat

for the Pennant to fire, regardless of any connections

between “COMD” and “HTD”, but the Pennant will

not fire if this connection is broken.

Other Field Interlocks: Other safety switches

that are intended to prevent the Pennant from firing

(such as fan proving switches, powered louver end

switches, etc.) The terminals are marked “OTHER

INTS <COM> <NO>”. These terminals are shipped

with a jumper between them. Remove jumper to

use these terminals. The Pennant will not fire if this

connection is broken.

Advertising
This manual is related to the following products: