Low temperature pennant, Page 15, Figure 4. suggested piping - hydronic boiler – LAARS Pennant PNCV - Install and Operating Manual User Manual

Page 15

Advertising
background image

Low Temperature Pennant

Page 15

Figure 4. Suggested Piping - Hydronic Boiler.

THERMOMETER

SENSOR

TEMPERATURE

GLOBE VALVE

CHECK VALVE

LEGEND

W/ FAST FILL BYPASS

PRESSURE REDUCING VALVE

WITH AIR SCOOP AND
AUTO AIR VENT

EXPANSION TANK

3-WAY VALVE

Cold Water

Make-Up

VALVE

VALVE

PURGE

PUMP

ADDITIONAL REQUIREMENTS.

WITH LOCAL CODES AND ORDINANCES FOR

PIPING CONFIGURATION AND VALVING, CHECK

WARNING: THIS DRAWING SHOWS SUGGESTED

Pump

System

Supply

System

System

Return

C

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM.

PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS.

PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS.

BOILER WATER CONNECTIONS (INLET/OUTLET)
MAY VARY. VERIFY CONNECTION ORIENTATION.
BOILER CIRCUIT PIPING MUST BE EQUAL
BOILER WATER CONNECTION SIZE.

DIMENSION "C" TO BE 4 PIPE DIAMETERS.

DOTTED DEVICES INDICATE ALTERNATE
LOCATIONS.
TEMPERATURE SENSORS REQUIRE FIELD
INTERLOCK TO BOILER CONTROLS.

COMBINED FLOW OF ALL BOILERS.

COMMON PIPING MUST BE SIZED FOR

BOILER CIRC. PUMP SIZED FOR FLOW
THROUGH BOILER
FULL-SIZED PIPING.

AND 30 FEET OF

MINIMUM INLET WATER TEMP = 70°F

3-Way Valve

Mounted on Pennant

Pump Mounted

on Pennant

C

Figure 5. Hydronic Piping — One Boiler, Multi-Temperature System.

THERMOMETER

SENSOR

TEMPERATURE

GLOBE VALVE

CHECK VALVE

W/ FAST FILL BYPASS

PRESSURE REDUCING VALVE

WITH AIR SCOOP AND
AUTO AIR VENT

EXPANSION TANK

3-WAY VALVE

VALVE

VALVE

PURGE

PUMP

ADDITIONAL REQUIREMENTS.

WITH LOCAL CODES AND ORDINANCES FOR

PIPING CONFIGURATION AND VALVING, CHECK

WARNING: THIS DRAWING SHOWS SUGGESTED

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM.

PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS.

PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS.

BOILER WATER CONNECTIONS (INLET/OUTLET)

MAY VARY. VERIFY CONNECTION ORIENTATION.

BOILER CIRCUIT PIPING MUST BE EQUAL

BOILER WATER CONNECTION SIZE.

DIMENSION "C" TO BE 4 PIPE DIAMETERS.

DOTTED DEVICES INDICATE ALTERNATE
LOCATIONS.

TEMPERATURE SENSORS REQUIRE FIELD
INTERLOCK TO BOILER CONTROLS.

COMBINED FLOW OF ALL BOILERS.

COMMON PIPING MUST BE SIZED FOR

BOILER CIRC. PUMP SIZED FOR FLOW THROUGH
BOILER AND 30 FEET OF FULL-SIZED PIPING.

MINIMUM INLET WATER TEMP = 70°F

LEGEND

Cold Water

Make-Up

Pump

System

Supply

System

System

Return

C

3-Way Valve

Mounted on Pennant

Pump Mounted

on Pennant