Figure 6. Suggested Piping — One Water Heater, One Tank.

Table 9. Temperature Rise — Water Heater.

Size

GPM Water Flow

Temperature Rise °F

LPM Water Flow

Temperature Rise °C

Soft

Normal

Hard

Soft

Normal

Hard

Soft

Normal

Hard

Soft

Normal

Hard

500

45

68

90

19

13

9

170

257

341

10

7

5

750

45

68

90

28

19

14

170

257

341

16

10

8

1000

45

68

90

38

25

19

170

257

341

21

14

10

1250

68

68

90

31

31

24

257

257

341

17

17

13

1500

68

68

90

38

38

28

257

257

341

21

21

16

1750

68

68

90

44

44

33

257

257

341

24

24

18

2000

112

112

112

30

30

30

424

424

424

17

17

17

Notes:

Soft Water = 1 to 7.5 grains hardness

Normal Water = 7.6 to 17 grains hardness

Hard Water = more than 17 grains hardness

GPM = gallons per minute

LPM = liters per minute

certified for outdoor installations, such installations

are not recommended in areas subject to freezing

temperatures, unless proper precautions are taken.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,

etc., may prevent a heater from firing. Any time a

heater is subjected to freezing conditions, and the

heater is not able to fire, and/or the water is not

able to circulate, there is a risk of freezing in the

heater or in the pipes in the system. When water

freezes, it expands. This can result in bursting of pipes

in the system, or damage to the heater, which could

result in leaking or flooding conditions.

Contact the local factory representative or Laars

for additional information.